String Inverter
Input Side Data
220/380Vac
Max. PV input power
Max. PV input voltage
Start-up voltage (Voc)
Stop Voltage
MPP voltage range
MPP voltage range for nominal power
No. of MPPTs
Max. number of PV strings per MPPT
String Fuse
Max. PV operating current
maximum DC short circuit current
Max. current for input connector
Arc Flash Detection
DC Disconnect
Insulation Detection
DC Surge Arrestor
65000W
1000V
620V
540
550~950V
550~850V
1
8
Positive and Negative
120A
200A
25A
Standard
Standard
Yes
Type II DIN rail surge arrester
Output Side Data
Nominal AC output power
Max AC output power (PF=1)
Max. AC output apparent power
Max. AC output current
Nominal AC voltage
AC voltage range
Nominal grid frequency
Grid frequency range
THD
DC current injection
Power Factor@FL
Power Factor Range
AC Maximum Cable Size
AC Surge Arrestor
AC Leakage Current Detection
AC Disconnect
60000W
63360W
63360VA
96A
3Ǿ/3W, 220/380Vac
295~456Vac
60Hz
55~ 65Hz
<3% (Nominal power)
<0.5%In
>0.99@default value at nominal power
0.8LG-0.8LD
0AWG, Cu or Al
Type II DIN rail