Cold Link Africa October 2026 | Page 6

He stresses that food loss is not primarily a farm production problem; the breakdown happens in the cold chain. Inadequate on‐farm and rural cold infrastructure, unreliable power and policy gaps turn good harvests into waste, squandering nutrition, land, water and energy, squeezing farmers and pushing up consumer prices.

The first and most critical step is pre‐cooling. Produce is typically harvested at 23 – 24 ° C and must be cooled rapidly to around 4 – 5 ° C in a dedicated pre‐cooling facility to preserve shelf life.“ That is probably the most critical step for produce in its life cycle and this is also where the majority of food losses happen.”
Many farmers have no pre‐cool facilities, cannot power them reliably, or must haul produce hundreds of kilometres to shared cold rooms. However, where pre‐cooling is available, the chain should then run seamlessly through cold storage at farms or packhouses, refrigerated transport and finally retail refrigeration in display cabinets and walk‐in rooms. Small-scale farmers, who often rely on municipal fresh markets, have little control over how their produce is cooled and handled along the way.
For Dreyer, cutting food loss demands consistent standards across this whole chain – temperature, hygiene and energy performance – rather than piecemeal upgrades at individual points.
NETWORKING BUSINESS ANALYSIS

Building an efficient cold chain for food security in Africa

By Eamonn Ryan
At a recent cold chain event, Louwrens Dreyer, sales engineer at Danfoss Climate Solutions, unpacked how inefficient cold chains are driving food losses in South Africa and even more so across the continent – and what practical technical, energy and policy interventions can change that.

He stresses that food loss is not primarily a farm production problem, the breakdown happens in the cold chain. Inadequate on‐farm and rural cold infrastructure, unreliable power and policy gaps turn good harvests into waste, squandering nutrition, land, water and energy, squeezing farmers and pushing up consumer prices. The first and most critical step is pre‐cooling. Produce is typically harvested at 23 – 24 ° C and must be cooled rapidly to around 4 – 5 ° C in a dedicated pre‐cooling facility to preserve shelf life.“ That is probably the most critical step for produce in its life cycle and this is also where the majority of food losses happen.”

Many farmers have no pre‐cool facilities, cannot power them reliably, or must haul produce hundreds of kilometres to shared cold rooms. However, where pre‐cooling is available, the chain should then run seamlessly through cold storage at farms or packhouses, refrigerated transport and finally retail refrigeration in display cabinets and walk‐in rooms. Small-scale farmers, who often rely on municipal fresh markets, have little control over how their produce is cooled and handled along the way.
For Dreyer, cutting food loss demands consistent standards across this whole chain – temperature, hygiene and energy performance – rather than piecemeal upgrades at individual points.
AFRICAN REALITIES: HEAT, DUST AND UNSTABLE POWER
Although the vapour compression cycle is universal, Dreyer argues that Africa’ s operating conditions demand a different mindset. Ambient temperatures of 32 – 42 ° C, often with difficult humidity levels, fundamentally affect system design.
“ Tzaneen and Cape Town are not the same place, and that is where our engineers need to be flexible in selecting the correct refrigerants and the correct compressors and systems to accommodate these areas.” What works at European test conditions may fail in the Lowveld or Northern Cape. Compressor selection, refrigerant choice and capacity must be based on real local climates.
Dust is another silent enemy. Many packhouses sit on dirt roads; condensers near these routes quickly clog, throttling airflow and causing poor pull‐down and nuisance tripping. Dreyer says he has repeatedly traced‘ inefficiency’ complaints back to dust‐blocked condensers, not bad equipment.
Power instability is, in his view, the biggest structural threat. Rural farms often rely solely on the grid, with long delays when faults occur, forcing them to run generators for many hours a day. He cites Western Cape packhouses that, at the height of recent crises, were spending millions of rand a day on diesel. Capital that should fund new cold stores, controls or efficient compressors is burned in generator exhausts, quietly stalling growth and modernisation across the industry.
DESIGNING FOR ENERGY EFFICIENCY
For Dreyer, energy efficiency sits at the heart of a resilient cold chain, not at the periphery.“ Energy efficiency is not just a component of the cold chain, but it’ s probably the most critical part.”
He starts with the basics. Insulation must be correctly specified for the application and climate; there is little sense investing in advanced electronics and compressors if they are wrapped in outdated or inadequate insulated panels. Thermal bridging and poor detailing undermine performance before the plant even starts.
“ Air sealing is another major factor. The moment warm, moist air keeps entering a cold space, you’ re adding a constant hidden heat load. With proper doors, fast‐acting mechanisms and even simple measures like strip curtains, you can dramatically
INCORPORATING COLD CHAIN
Louwrens Dreyer, sales engineer at Danfoss Climate Solutions.
cut infiltration and compressor run time.
“ On the plant side, efficient motors and variable speed drives let your capacity follow the actual load. If a warehouse is designed for 8 000 pallets but most days you’ re only running at 5 000, it shouldn’ t be operating at full power. Variable speed drives( VSDs) on compressors and fans allow the system to back off when demand is lower, which cuts energy use and wear. Without that kind of modulation, you’ re simply wasting power,” says Dreyer.
He notes that how a plant is operated matters as much as how it is built. Running stores beyond their design throughput or ignoring peak versus off‐peak operation quickly erodes efficiency. He urges owners to track simple indicators such as COP( Coefficient of Performance) and kWh per cubic metre or per ton transported so they can spot under‐ performing sites and justify upgrades.
POWER QUALITY, SOLAR AND MICROGRIDS
Given South Africa’ s grid realities, Dreyer believes it is naïve to talk about cold chain reliability without addressing power quality and alternative supply. On grid‐connected sites, he recommends basic electrical protection as standard: voltage stabilisers, phase protection relays and time delays that ensure compressors and drives only restart once voltage and phase conditions are stable. This reduces failures of sensitive electronics and avoids the damage that can result from sudden phase reversals and repeated short cycling.
“ Solar power is a natural fit for on‐farm cold rooms, especially all the 4 × 4 and 6 × 6‐metre units out there. We’ re already world leaders in solar installations and design, and we need to use that same skill to design our own refrigeration systems.
Kamran Aydinov | Magnific. com
© Cold Link Africa

6

COLD LINK AFRICA October 2026