Practical lessons in fan coil unit design and installation
By Eamonn Ryan, from a presentation by Nols Lubbe, general manager, AERSA( AERMEC)
Fan coil units may be among the most familiar components in commercial air-conditioning systems, yet they are frequently affected by poor selection, incorrect installation and avoidable maintenance problems.
Speaking at the July technical meeting of the SAIRAC Cape Town Centre, Nols Lubbe drew on nearly four decades of industry experience to share practical lessons that can improve both system performance and long-term reliability.
With a career spanning consulting engineering, contracting, project management, commissioning, service and equipment sales, Lubbe has encountered fan coil unit( FCU) installations in virtually every type of commercial building. Rather than presenting a purely theoretical discussion, he focused on the practical issues that repeatedly arise in the field, from equipment selection and condensate drainage to hydronic balancing and maintenance access.
Lubbe began by distinguishing between fan coil units and air handling units( AHUs), noting that although the two are often confused, they perform different functions. An AHU is generally a customengineered system capable of supplying multiple areas through extensive ductwork while incorporating features such as filtration, humidification, heat recovery and sophisticated controls. A fan coil unit, by comparison, is typically a factory-built product intended to provide local heating or cooling to a single room or small zone, usually with minimal ducting and limited external static pressure capability.
One of the advantages of fan coil units is the ability to provide individual room temperature control. Hotels, offices and similar buildings can therefore offer occupants greater comfort while avoiding the complexity of conditioning large areas from a single central air-handling system.
CHOOSING THE RIGHT CONFIGURATION
Lubbe outlined the range of FCU configurations commonly encountered in commercial buildings. Concealed horizontal ceiling units remain the most widely used, particularly in offices where they are installed above suspended ceilings and connected to short duct runs. Vertical floormounted units continue to find application where ceiling space is limited, while highwall and cassette units provide compact solutions in smaller offices or areas where extensive ductwork is undesirable.
He also highlighted newer drawer-type designs that allow the entire fan, coil, filter and valve assembly to slide out from the front of the unit. This significantly improves serviceability, particularly in hotels and similar applications where access above ceilings is often restricted.
Whatever the configuration, Lubbe stressed that maintenance requirements should be considered during the design stage rather than after installation.
He dealt with the differences between draw-through and blow-through fan coil arrangements. In a blow-through unit, the fan is positioned upstream of the cooling coil, placing the coil and condensate tray under positive pressure. This assists condensate drainage and generally eliminates the need for a U-trap at the drain connection. Drawthrough units operate differently. Here the fan is positioned downstream of the coil, creating negative pressure across the condensate tray. Without a correctly sized U-trap, air is drawn into the drain line instead of allowing condensate to discharge freely, often resulting in overflowing drip trays and water damage.
Lubbe noted that many drainage problems encountered in practice stem not from defective equipment but from overlooking these basic design principles during installation.
MORE THAN A FAN AND A COIL
The coil remains the heart of the system, while the casing should be properly insulated to prevent external condensation and unwanted heat gain. Modern units increasingly employ electronically commutated( EC) motors to improve efficiency and provide more precise speed control.
Where electric heaters are incorporated, safety becomes critical. Lubbe emphasised that heaters should be wired using heat-resistant cable and protected by both manual and automatic reset safety thermostats. He cautioned that these safety devices must remain readily accessible, warning that bypassing them after nuisance trips has, in the past, contributed to serious fires.
Similarly, filters should be viewed primarily as protection for the coil rather than as comprehensive air-cleaning devices. Where high indoor air quality is required, appropriate filtration should instead be provided within dedicated fresh-air or airhandling systems.