This becomes particularly important in large cold stores, packhouses, controlled-atmosphere( CA) facilities and forced-air precooling installations, where thousands of bins or pallets may need to be cooled and maintained within relatively narrow temperature ranges. For these applications, fans, evaporators, ducting, curtains and airflow controls form an interconnected system. Getting the selection and arrangement right is less about moving the maximum possible volume of air and more about understanding what the product and facility require.
South Africa ' s fruit industry provides some useful examples of this approach. The South African Postharvest / Hortgro material notes that air management is as important as temperature management in fruit cooling, particularly because inadequate circulation can result in temperature gradients within a store.
The first consideration is what the air is being asked to do. During forced-air precooling, the objective is to remove field heat quickly. This requires air to pass through the product rather than simply circulate around it. Hortgro explains – and
|
Cold Link Africa itself covered this in the project article in the September issue – that cold air naturally follows the path of least resistance. If gaps exist between pallets or around a load, air can bypass the cartons, leaving product at the centre of the load warmer than the surrounding air. Forcedair systems therefore use a pressure difference to draw air through ventilated cartons and the produce they contain. This makes the pallet and packaging part of the cooling system.
Ventilation openings in cartons, pallet configuration, load density and the sealing of the forced-air tunnel all affect resistance to airflow. Hortgro ' s guidance consequently treats tunnel design, airflow requirements and pressure losses as engineering considerations rather than simply installation details. The distinction becomes even more important once precooling has been completed.
A storage system has a different job from a forced-air precooler. It needs to remove ongoing heat loads and maintain a relatively uniform environment without unnecessarily drying the product or consuming energy moving excessive volumes of air.
Hortgro notes that fans used for forced-air cooling should be stopped once the required product temperature has been reached, helping to limit moisture loss
|
and potential chilling or freezing injury.
The operating strategy therefore needs to
reflect the product and process rather than
applying the same airflow continuously.
DESIGNING FOR LARGE STORES
The challenge becomes more complex
as cold stores grow. The South African
Controlled Atmosphere Storage Operators
Manual provides practical guidance based
on local commercial storage. In a standard
1 040-bin cold store, for example, four axialflow
fans were used to distribute air, with
two fans serving each cooler block. The
manual gives an airflow of approximately
15 000m ³/ h per fan at a static pressure of
10mm water gauge, with an absorbed motor
power of about 1kW per fan.
The figures themselves are less important
than the design principle behind them. Large
stores need sufficient circulation to prevent
temperature stratification, while the layout
has to encourage air to travel through the
intended storage volume. The same manual
describes the use of curtains to limit shortcircuiting
and improve distribution around
the stored bins.
This illustrates why simply specifying a
fan according to its free-air capacity can
be misleading. The actual operating point
depends on the resistance presented by
the cooler, ductwork, storage arrangement
and other components. Fan selection
therefore needs to be linked to the
pressure and volume requirements of the
complete system.
|
THE EVAPORATOR IS PART OF THE EQUATION
The evaporator is often considered primarily in terms of its refrigeration duty, but its air-side performance can have a significant influence on the overall installation. Coil pressure drop, fan efficiency, discharge arrangement and air volume all affect how effectively the cooler operates within the room.
A South African project involving Betko ' s controlled-atmosphere stores – recorded in Cold Link Africa October issue- provides a particularly useful example. GEA reports that variable-speed evaporator fans were initially considered as an obvious route to reducing energy consumption. Experience at an earlier site, however, showed that reducing fan speed too far could result in hot spots and wilting. The issue was therefore not simply how little fan power could be used, but how refrigeration performance, air volume and product requirements could be balanced.
The eventual approach involved optimising the complete blower-coil arrangement. GEA reports that adjustments to evaporation temperature, fan volume and pressure drop contributed to the solution. A redesigned fan inlet cowling also reduced absorbed fan power by a reported 2 – 3 %. The example is significant because it demonstrates where much of the opportunity for efficiency lies: not necessarily in one component, but in reducing the resistance and inefficiencies throughout the air side.
|