Cold Link Africa May 2019 | Page 15

PROJECT INCORPORATING COLD CHAIN pressure transducer control on the lead included the blast freezers), a multiplex compressor. refrigeration plant (plant C) was Each of the rooms connected to installed, which consists of three Bitzer plants A and B were then outfitted semi-hermetic compressors with a with two HC evaporator coolers, with total capacity of 100.5kWR and an capacities ranging from 7kWR to evaporation temperature of -32°C. This 30kWR, depending on their specific would provide lower temperatures of up requirements. However, there were a to -25°C for the blast chillers. In addition, rooms 9 and 10 would handful of exceptions since it was found that the existing coolers in some of the be connected via a satellite Bitzer rooms could be integrated into the new compressor with a capacity of 31.5kWR, system (which saved some costs). positioned on the same receiver base. With an evaporation temperature of Again, HC evaporator coolers were -7°C, plants A and B supply refrigeration installed in each of the five rooms to all the rooms, except for five rooms that on plant C’s circuit, with capacities demanded a more heavy-duty solution. ranging from 8.5kWR to 23kWR. Each For rooms 3, 6, and 8 (which 2 of the coolers in all 28 of the facility’s 1 3 1. Evaporators in the processing area. 2. The water filtration system. 3. Inside the bacon packing area. 4. Smoke room. 4 COLD LINK AFRICA • May 2019 www.coldlinkafrica.co.za 15