PROJECT INCORPORATING COLD CHAIN outdoor wet bulb. The system is designed to reduce fogging and ice surface condensation. Relative humidity at, or below, 80% with ice rink temperatures between 5°C and 15°C is usually sufficient to eliminate fogging. However, condensation can occur on the ceiling or roof structure due to radiation from the building structure to the ice. Low relative humidity is maintained in this system to reduce this condition when the high emissivity ceiling is exposed to the ice surface. Since the ice’s surface temperature cannot be measured easily, the ice condition is customarily controlled from predetermined coolant average temperature and from the ice temperature measured by the thermocouple embedded beneath the ice surface. With approximately 7°C air temperature and 50mm ice thickness, ice at -6.5°C to -5.5°C is satisfactory for hockey, -4°C to -3°C for figure skating, and -3°C to -2°C for recreational skating, says Vuletic. CLA Getting the plant ready for transport to Ilanga Mall. List of professionals Client Resilient Properties Quantity surveyors BJV Architects LPA Civil and structural engineers Breet Construction HVAC consulting engineers WIN Consulting Engineers Refrigeration consulting engineers EP Multistage Cooling Ice arena operators Tri Ice Sports Holdings Equipment Rigging of the skid into the plant room. Compressors GEA Africa Condenser Vahterus Chiller Vahterus Cooling tower BAC Glycol pumps Grundfos Water pump Grundfos Ammonia separator Ilva General Engineering Electrical MCC Industrial Motor Control (IMC) Rink piping Macsteel Heat recovery Star COLD LINK AFRICA • May 2018 www.coldlinkafrica.co.za 23