INCORPORATING COLD CHAIN
PROJECT
• Increase cooling capacity
• Improve energy efficiency
• Move to a more sustainable, natural‐refrigerant solution
The system had to serve three distinct temperature zones with appropriate capacity and control. The ice‐cream freezer room operates at around-25 ° C, the main freezer room at approximately-20 ° C, and the dock area – functioning as the in‐ and outbound receiving section – between 0 and 2 ° C.
To meet these needs, the new plant was engineered with a low‐temperature capacity of roughly 56kW and a medium‐temperature capacity in the region of 300kW. Dorin CD 335 1B compressors were selected for the low‐temperature side, and Dorin CD 501M compressors for the medium‐temperature duty.
On the refrigerant side, the practical choices at this scale were ammonia or CO₂. Given the size and configuration of the site, and the particularities of Californian policy and environmental codes – alongside the global phase‐down of high‐GWP gases – CO₂ emerged as the more appropriate option. It offered a natural, low‐GWP refrigerant with excellent performance, without the additional complexities that an ammonia solution would have introduced for this particular facility.
Serviceability formed another crucial part of the brief. Sysco wanted reassurance that once the plant was commissioned, there would be competent local support for day‐to‐day operation and maintenance. IHG Mechanical’ s background was primarily in ammonia and freon, and this was their first CO₂ project. The design therefore needed to lend itself to training and straightforward servicing, with clear component layouts and a coherent control philosophy.
INSIDE THE PLANT: FROM CRS SKID TO COLMAC EVAPORATORS
The heart of the installation is a factory‐built CO₂ rack supplied by CRS. In North American terminology this is a‘ skid’, but effectively it functions as a complete plant room in a single IP65‐rated enclosure. All major mechanical and electrical components – compressors, oil management, gas cooler, vessels, controls and switchgear – are integrated inside the skid.
One of CRS’ s distinctive features is its‘ Switch’ concept: the enclosure has robust doors that can be opened like normal cabinet doors or removed completely and parked to one side, giving excellent access for installation and maintenance. The doors are re‐fitted, they align cleanly, preserving the unit’ s integrity and weather protection. The aim is a true drop‐in solution: crane it into place, connect services and commission.
Within the skid, Dorin compressors carry out the compression work for both the medium‐ and low‐temperature suction groups. Oil separation and management are handled by a Temp‐Rite oil system, well suited to CO₂’ s higher pressures. Oil filters, separators and regulators are arranged for easy monitoring, with pressure gauges and transducers positioned where commissioning and service engineers can readily see them.
On the high‐pressure side, the plant uses a gas cooler rather than a traditional condenser. This is standard practice for CO₂ systems: instead of condensing the refrigerant in the conventional sense, the gas cooler reduces the temperature of the high‐pressure gas. Pressures of the order of 80 – 90 bar on the high side are dropped to about 38 bar by a high‐pressure valve into a separation vessel. Its main function is to separate the liquid and vapour portions after the pressure reduction.
To secure efficient operation in California’ s often high ambient temperatures, CRS integrated an adiabatic gas cooler. Wet pads on the sides of the cooler are supplied with water so that incoming air is pre‐cooled by evaporation before it passes through the heat‐exchange coil. This reduces gas cooler outlet temperature under hot conditions and supports stable operation and good efficiency when the ambient soars.
From the skid, stainless‐steel piping distributes refrigerant to the various cold rooms. Each evaporator circuit is served by four key lines: a liquid line, a suction line, a hot‐gas line for defrost and a hot‐gas return line. On the roof, valve stations with actuated valves manage the mode of operation. In normal cooling, the expansion device and suction line are open while the hot‐gas lines are closed. During defrost, the hot‐gas and hot‐gas return lines are opened and the cooling path is isolated. These valve stations are mounted on a soft, protective surface on the roof, with vertical drops into the relevant rooms below.
The evaporators themselves were supplied by Colmac. The dock‐levelling area and both freezer rooms use Colmac air coolers designed for the respective temperature levels, all equipped with hot‐gas defrost.