PROJECT INCORPORATING COLD CHAIN reclaim. The medium-temperature cycle will operate in a trans-critical manner in high-ambient temperatures where the condensing pressure is above 72 bar or 31°C. When operating in this state, the refrigerant is unable to condense into a liquid. Below a condensing temperature of 31°C, the medium-temperature cycle will operate in a subcritical manner; this means that the refrigerant will condense to a liquid and the discharge pressure will vary between 55 and 70 bar. The head pressure varies according to ambient temperature and is controlled via the Danfoss controllers installed. When the system is unable to condense below 72 bar and to condense CO 2 to a liquid, a high-pressure expansion valve is used. In the case of Danfoss, the device is known as the ICMT valve. The pressure in the gas cooler leaving as well as the outlet temperature are calculated to vary the opening of the ICMT. The pressure in the receiver is maintained at 38 bar, or 3.3°C where CO 2 exists as a liquid. The liquid is then fed to the evaporator coils where direct expansion occurs. The medium-, low-, and intermediate- temperature cycles are equipped with a common oil management system, which ensures that the refrigeration compressors stay lubricated. The system is of a closed loop configuration type and only requires maintenance should contamination occur. The oil management system has built-in safeties that automatically switch the compressors off when it senses low or no oil levels and automatically resets once minimum oil level has returned. All switch gear for the packs are situated in the main board within the plant room and within the pack boards that are situated on the packs themselves. All controls that operate the evaporator coils in the store are situated within the store at each individual coil respectively. Each compressor is fitted with a manual overload and thermistor, which will protect the compressor electrically; should this fail, it usually indicates a faulty compressor and a technician will be required before resetting. The heat reclaim to supply hot water can be connected through the discharge of the medium-temperature cycle and is piped in such a manner that the heat exchanger could be bypassed with the help of a three-way ball valve. A signal is received when heating is required and in turn, this opens the three-way ball valve so that hot water is generated and supplied. The hot water can be controlled to a temperature close to boiling point. The medium-, low-, and intermediate- temperature racks are fitted with low- and high-pressure safety switches, which will stop the cycle if the operating pressures are out of the desired set-points. Should the physical safeties trip, a technician will be required to manually reset and check that the system is safe to operate. Due to the high operating pressures of CO 2 , the pack controller is set up so that it will stop certain compressors should the discharge pressure and/or temperature of the cycle exceed the safety limits and eventually, it will stop the whole cycle should the problem not resolve itself. Bitzer compressors were used in the CO 2 refrigeration packs. Hot water exchanger. Woolworths Kyalami chose to go with CO 2 for their refrigeration needs. The controllers are fitted with pressure transducers, which the controller reads to calculate the operating parameters. When the pressures are within the desired range, the cycle will start up automatically. Every pack and its specific controllers are connected to a main safety circuit that will stop all refrigeration completely if none of the compressors are safe to run. The safety circuit will be de-energised, preventing migration of the refrigerant. With CO 2 , this can occur in a very short period and can cause excessive pressures, relief valve blow-offs, and very high start-up loads in the system. Pressure relief valves are fitted on critical main pipelines and receiver to relieve pressure when necessary; this is to ensure the safety of the valves and the components fitted in the refrigeration cycle. CO 2 sensors are installed in the plant room and on the floor area, which will detect a leak and sound an alarm if the CO 2 concentration gets too high. The sensor in the plant room will activate an extraction fan when the concentration of CO 2 within the plant room gets too high. CLA List of professionals Owner   Woolworths Developer Iguana Architect / Designer  R&L Project manager   Consulting engineers Contractors Product suppliers  40 Woolworths Electrical RWP Mechanical CRS | WSP Wet services and civil Iguana Main building Iguana HVAC&R Iguana Wet services Iguana Electrical RWP Refrigeration CRS Refrigeration plant CRS Condensers HC Heat Compressors Bitzer Electronics Danfoss  Underfloor heating Pioneer Floor Heating A Danfoss system manager, case, and pack controllers have been used to ensure that the refrigeration cycle is continuously run at optimum performance. www.coldlinkafrica.co.za COLD LINK AFRICA • January/February 2019