Cold Link Africa January/February 2018 | Page 23

PROJECT INCORPORATING COLD CHAIN Continued from page 21 The refrigeration plant has a low-stage operating capacity of 480kWR and high-stage operating capacity of 1 486kWR. REFRIGERATION PLANT DETAILS The upgraded refrigeration plant has a low-stage operating capacity of 480kWR and high-stage operating capacity of 1 486kWR. There are two low-stage duty compressors, two high-stage duty compressors, and a swing compressor. The accumulator vessels have been designed to allow for future expansion of the refrigeration plant. Two ammonia to glycol plate heat exchangers are used to cool down the glycol, which is then pumped to the various glycol-cooled rooms mentioned above. Two new Evapco induced draft condensers were installed, with close- coupled, mono-block-type circulating pumps that circulate water over the galvanised coil. A closed-loop cooling circuit for the compressor oil is also installed in each unit. LIST OF PROFESSIONALS Owner Massmart / Wallmart Architect / Designer R&L Quantity surveyor MLC Consulting engineers Contractors Electrical WSP Mechanical WSP Refrigeration Marine Refrigeration Engineering (MRE) Main building Edilcon Construction Panelling Rudnev Steel supply Ferro Electrical Qualect Heat rejection rate: 923kW (each) Condensing temperature: 34°C Wet bulb temperature: 20°C TIGHT DEADLINES Sufficient and regular communication between subcontractors on site is always a crucial aspect to ensure efficient production from all parties, explains Charles van der Walt of MRE Gauteng. “Finding the solution to the primary steelwork misalignment above the cold rooms was a good example of this. “Keeping in mind that everyone needs to work as a team to finish a project on time, moving away from the immediate blame-shifting, and moving towards a positive mindset to create innovative solutions to unexpected problems, is vital for the successful completion of any project,” says Van der Walt. CLA Ammonia and glycol chiller valve stations. Outside MassFresh Meat’s new ammonia plant room. The -10°C and -34°C accumulator skids complete with plate heat exchangers, ammonia pumps, and gauge panel. The three KSB glycol pumps. COLD LINK AFRICA • January | February 2018 www.coldlinkafrica.co.za 23