4 6
5 system for the storage of finished product and the manufacturing of dips and meze.
The seafood plant, installed in 2006, is charged with R404A, which had been a viable refrigerant at the time.
The new CO 2 plant has a trans-critical booster pack with parallel compressors. The pack manufactured in the Ottery workshop of Mainstream Refrigeration has seven Frascold semi-hermetic compressors, all fitted with variable frequency drives( VFDs) for capacity control. Three compressors operate on the medium temperature( MT) circuit(-7 ° C), two on the low temperature circuit(-32 ° C), and two provide parallel compression on the MT. The MT circuit maintains the temperature( 0 – 4 ° C) in five cold rooms, three double-blast chiller tunnels, and a blast chiller.
The LT circuit has a blast freezer that can also operate as-25 ° C cold room.
The discharge from the MT compressors is piped to a plate heat exchanger fed with water from three air-cooled( piped in parallel) finned coolers connected to the municipal water mains. The horizontal coil coolers each have four EC fans, which are speed controlled and / or cycled to maintain required system pressures. Water from the CO 2 plate heat exchanger feeds a 1 000-litre tank as a buffer for a constant supply of water at 40 – 45 ° C to the many hand-washing points, production cookers, and for plant cleaning.
All evaporator coils are direct expansion( DX) with copper tubing and aluminium fins and fitted with AC fan motors.
IN-HOUSE SKILLS TRAINING
“ Since doing our first CO 2 plant in 2009, we have come a long way in the design and installation of CO 2 systems,” explains
1.
The pumps for the cooling water circulation have 100 % backup and are fitted with VFDs.
2.
Hygiene standards are strictly controlled throughout the production area and all staff must
wash hands and change into boots before entering.
3.
Lourens van Staden( senior technician) on left with Richard Drinkrow, MD of Mainstream
Refrigeration.
4.
Pressure cookers in the production area.
5.
The 1 000-litre make-up tank is connected to the municipal mains.
6.
At the Danfoss ICMTS valve( grey coloured), the high-pressure CO 2 gas has a phase
change to liquid.