PROJECT INCORPORATING COLD CHAIN 1 4 5 2 3 airlock. The cooling tunnels were designed to operate with a coil air off temperature of -1°C, the chillers at an average air temperature of +2°C to +4°C, and the airlock at +12°C. Four high-stage reciprocating compressors were designed to meet the facility load and operate at saturated suction and condensing temperatures of between -8°C and +34°C, respectively. Three compressors were required to run under peak conditions, with a fourth as standby. The compressors operate at a fixed speed of 1 450rpm. Two evaporative condensers were installed on strip plinths on top of the new plant room roof and together, the condensers operate at a saturated condensing temperature of +34°C. With one condenser out of operation, the saturated condensing temperature will rise to +37°C. One horizontal -8°C accumulator vessel is provided for the plant as well as one receiver vessel. CONTROLS The refrigeration plant is equipped with an automated control system to ensure that the starting, stopping, and capacity control is fully automated. The refrigeration plant isn’t manned, and the control system therefore accommodates this. In addition, the control system has the facility to allow for plant monitoring, including all room temperatures and cooling tunnel temperatures from the client’s operations office. The control system also accommodates data logging for temperatures and pressures throughout the refrigeration plant. This data is readily available in the form of tabulated or graphical display. The control system even sends text messages via the cellular networks to select phone numbers for plant alarm conditions. The cooling tunnels make use of proportional suction control valves to maintain temperatures for export goods accurately. This control allows for the fastest cool-down rate with least amount 1. Motors powering the Mycom N8M ammonia compressors in the plant room. 2. The accumulator, gauge panel, and ammonia liquid make-up line. 3. A Mycom N8M compressor. The Mycom packages produced by MRE are fitted with an internal relief valve (a SANS 10147 requirement). This is one of many robust safety features on the compressors. 4. Proportional expansion valves are used on the suction side of the valve station to control evaporating pressure precisely. 5. Airlock valve station. 6. Walkway between the two large chillers. Valve stations for the chiller to either side. 7. The airlock and additional rapid cooling tunnels. Product ready to be loaded. 7 6 COLD LINK AFRICA • October 2018 www.coldlinkafrica.co.za 25