SISTEMA COMBINATO ENERGY PLUS
POTENZA ELETTRICA 2234 kW - POTENZA FRIGORIFERA 1780 Kw a -10 °C
COMBUSTIBILE METANO O SYNGAS
DIAGRAMMA, POTENZE, TEMPERATURE, PORTATE, SONO PURAMENTE INDICATIVE
7558 kWht
-10 °C
-10 °C
5 °C
1894 kWe
C1
°C
352 kWt
H=95 kcal/kg
G
TV 1
TURBOSTEAM
PS 25
CONDENSA
95 °C
5500 kg/h
95 °C
LIQUIDO
3424 kWt
H2O
H2O
95 °C
IN
D
250 kWe
29 °C
34 °C
3 bar(a)
GENERATORE
A
T
IV
O
95 °C
95 °C
°C
13
3,
7
RETTIFICATORE
H=630,36 kcal/kg
5500 kg/h-3 bar(a)
3 bar(a)
IC
SOLUZIONE
ASSORBITORE
LIQUIDO
H2O
34 °C
34 °C
TORRE EVAPORATIVA
3424 kWt
ARIA
29 °C
M
95 °C
CONDENSATORE
REFRIG.
3315 kWt
574 °C
CALDAIA INDIRETTA VAPORE
34 °C
H=668,48 kcal/kg
-5 °C
T REC
T HP
29 °C
95
AI PROCESSI INDUSTRIALI
1364 kWhf
4000 kWt
-5 °C
DEUMIDIFICAZIONE
196 kg/h
REFRIGERATORE AD ASSORBIMENTO NH3
178O kWf - ALIMENTAZIONE 3424 kWt
-10 °C
150 °C
TURBOGAS OP16
THERMO CHILLER
-5 °C
G
TG 1
VAPORE
EVAPORATORE
H=150 kcal/kg
COMB.
ARIA 35°C
32000 kg/h
416 kWhf
22 bar(a)
29 °C
ARIA
H2O
29 °C
Questo sistema trigenerativo combinato consente di produrre potenza elettrica (2234 kW) e potenza frigorifera (1780 kW) a -10 °C,
una parte della quale (416 kW) viene utilizzata per il raffreddamento dell’aria comburente della turbina gas affinchè assuma una
temperatura di 5°C costante tutto l’anno. Il rendimento aumenta considerevolmente. I gas esausti della turbina vengono utilizzati
per produrre 5500 kg/h di vapore a 22 bar necessari per alimentare una turbina vapore da 250 kWe. Il vapore esce dalla turbina,
dopo il salto di pressione, a 3 bar ed alimenta il generatore del ciclo ad assorbimento per produrre acqua refrigerata a -10 °C. 1364
kW frigorifere vengono rese disponibili per le utenze industriali.
TURBOGAS OP16
TURBOSTEAM PS25
THERMO CHILLER