AMF AMF Users Manual | Page 31

31 AFM® grade 0 Performance. All the data for AFM® has been established without the application of coagulants or flocculants. It is important to note that AFM® grade 0 can be used as an effective Cryptosporidium oocysts barrier at water flows of 2m/hr with a 900mm bed depth. When AFM® is combined with coagulation and flocculation using PAC (polyaluminium chloride) or Polyamide cationic flocculants, the performance and ability to remove cryptosporidium oocysts at 5 microns and sub 1 micron is greatly enhanced. The performance data presented is without the application of flocculants. 4 micron particle filtration performance Filtration performance % Water flow 99.96% 2m/hr 99.89% 5m/hr 99.85% 6m/hr 99.75% 7m/hr 99.54% 10 m/hr 3 micron particle filtration performance Filtration performance % 99.93% 99.80% 99.75% 99.61% 99.30% Water flow 2m/hr 5m/hr 6m/hr 7m/hr 10 m/hr filtration performance at a water flow of 2m/hr Filtration performance % 99.96% 99.93% 99.80% 99.60% Micron rating 4um 3um 2um 1um