Sound levels dB(A) Sound power level 48EN/EH 241 321 361 242 322 362 420 485 540 600 Total dB(A) 90 90 91 88 88 89 94 95 95 95 Sound pressure level Measurement conditions: in free field, measured at a distance of 5 metres, directivity 2 and at 1.5 metres from the ground. 48EN/EH 241 321 361 242 322 362 420 485 540 600 Total dB(A) 63 63 64 61 61 62 67 67 67 67 Note: The sound pressure level depends on the installation conditions and, as such, it only indicated as a guide. Values obtained according to the ISO 3744 standard. Operating limits Inlet air conditions Cooling Heating Minimum 14ºC WB 10ºC Maximum 22ºC WB 27ºC Minimum 12ºC * -10ºC WB *** Maximum 48ºC ** 15ºC WB - -30ºC Indoor coil heat pump Outdoor coil heat pump Gas burner Minimum * ** *** With a condensation pressure control operating down to -10ºC. With high powered axial fan operating up to 52ºC. With outdoor temperatures below -8ºC WB it is compulsory to select the anti-freeze protection option for the electric panel. AIR TREATMENT PLEASE CONSULT YOUR SALES REPRESENTATIVE FOR DRAWINGS 844 C A R R I E R 2 0 1 6 / 2 0 1 7