Dimension schemes for the STD version
30PA/PAC - 120STD / 160STD / 180STD with VERTICAL supply, M01
assembly (mm)
35
760
R2
R1
R4
110
COOLING
1166
R3
110
35
700
65
65
1387
860
894
1754
1727
6
85
Z
111
5
LEGEND
1128
134
696
1398
134
163
VERTICAL outdoor circuit air supply
Y
0,5m
Outdoor circuit air return
Electric panel
128
513
1m
202
Water outlet from the recovery circuit (optional)
4
Water inlet to the recovery circuit (optional)
5
Condensate outlet: trunk 3/4” M
6
Collapsible window for access to control panel (it
protrudes 12 mm)
567
3
1m
508
Water outlet from the indoor circuit
100
2
97
Water inlet to the indoor circuit
4
2
3
1
272
421
150
1,5m
X
Door switch
1
1201
312
Electric power supply
Note: the hidraulic connections 1 2 protrude 58 mm
Anti-vibration anchoring: rivet nut M10
Clear space to be observed for maintenance
operations and unit start-up
Models
120STD
30PA
30PAC
84
Centre of gravity coordinates (mm)
Reactions in the supports (kg)
X
Y
Z
Weight
R1
R2
R3
R4
625
399
676
379
89
112
101
77
160STD
619
400
666
397
92
119
107
79
180STD
625
397
674
396
93
119
105
79
120STD
645
402
673
410
99
117
107
87
160STD
639
402
663
428
102
124
113
90
180STD
646
400
669
429
104
123
111
91
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7