Unit components

High efficiency cooling circuits for R-410A
Electronic axial fans for low noise level
Possibility of thermal and acoustic insulation M0
Possibility of cooling recovery needs for renewal of air ( higher EER and COP )
Intelligent defrosting of outdoor coils
Assemblies with mixing box and free-cooling management
Indoor air quality using different combinations of gravimetric and opacimetric filters
Electronic plug-fans
Comfort / heating options : electrical heaters , hot water coil , gas burner ...
■■
Casing --
Casing made of galvanised steel metal with polyester paint , white colour RAL 7035 . Thermal insulation 9 mm thick , with fire classification M1 .
--
Self-supporting frame and access panels to the electric panel , compressors , fans , etc .
--
Cooling design :
• 1-air volume : models 90 to 180
• 2-air volumes : models 240 to 360
■■
Outdoor circuit --
Electronic EC axial fan ( s ) that adapt the rotation speed to the installation requirements , thereby reducing electricity consumption , the sound level at partial charge and improving the average seasonal output of the unit .
-- Coil with copper pipes and aluminium fins .
AIR TREATMENT
■■
Indoor circuit --
Electronic plug-fans directly coupled with variable speed and flow sensor . Facilities type of service industries consumption of fans associated with air transportation assumes a high % of the annual consumption of air conditioning . The use of fans of greater efficiency has a direct impact on the reduction of consumption .
-- Reusable air filters , assembled on a frame .
-- Coil with copper pipes and aluminium fins .
-- Condensates drain pan .
--
Thermostatic expansion valve ( s ) with external equalisation .
■■
Cooling circuit --
Hermetic scroll-type compressor in tandem design that improves the management of stages . Sound insulation , assembled over antivibration mounts . Control of phase equilibrium and the direction of rotation . Crankcase heaters .
-- Four-way cycle reversing valves ( heat pump units ).
-- Anti-acid dehydrating filter ( s ).
■■
Protections
--
High and low pressure pressostats .
--
Compressor discharge temperature control .
--
Non-return valve built into the compressor .
--
Main door switch .
--
Magnetothermic protection switches for the
compressor ( s ) power line and fan motor .
--
Automatic switch in the control circuit .
■■
Electric panel
--
Complete and fully wired electrical panel . Insulated
panel cover to prevent condensation . Protection IP55 .
--
Forced ventilation of the electric panel .
--
Transformer for power supply without neutral in
electrical panel .
--
Main ground connection .
--
Compressor and fan motor contacts .
822 C A R R I E R 2 0 1 6 / 2 0 1 7