AHI Carrier Catalog | Page 802

CARRIERrtc electronic control ( optional )
Electronic module with microprocessor comprised of a control board and a pGD1 graphic terminal installed over the unit electric panel and accessed using a polycarbonate collapsible window .
Optionally this terminal can be replaced by a TCO user terminal for installation inside of the premises . In this case the TCO terminal are not allowed to access parameters control and time schedule .
The management of the ambient temperature is controlled via a NTC ambient probe . This probe can be replaced by 1 or 2 RS485 probes .
In addition to the functions described in CARRIERrtc basic & medium control , this control allows controlling optional elements such as :
-- Cooling recovery circuit .
-- Electronic plug-fans .
-- Enthalpic or thermoenthalpic free-cooling .
-- Smoke detecting station .
--
Air quality probe for measuring CO2 and / or volatile compounds ..
-- Energy meter .
--
Refrigerant leak detector .
It also manages a local connection between units through a pLAN network (µ PC MEDIUM Local Area Network ), thus allowing communication of data and information for a maximum of 15 units . This enables the reduction of the number of pGD1 terminals , since a single shared terminal can monitor all control boards . It also allows to share the reading of some probes .
pGD1 terminal shared µ PC MEDIUM 1 µ PC MEDIUM 2 TCO µ PC MEDIUM 15 user terminal
Ambient probe CO2 probe Unit 1 ( master )
Unit 2 Unit 15
AIR TREATMENT

Optional

Optional for the outdoor unit 38NZ / NF
■■
Outdoor environment
Temperature --
Operation during all seasons via the condensation pressure control by damper ( up to -15 º C ).
Damper
Servomotor
Protection grille for the coil
Corrosion --
Coil with copper pipes and copper fins .
--
INERA ® coil with copper pipes and fins of an aluminium alloy , of high performance and great resistance to the corrosion .
--
Coil with copper pipes and aluminium fins with polyurethane and Blygold ® coating .
Humidity
--
Tropicalised electric panel .
--
Tropicalised motors and fans ( please consult ).
■■
Safety --
Soft starter of the supply fan which prolongs the set time mainly aimed at installations with cloth ducts .
■■
Installation --
Antivibration mounts made of rubber .
-- Service valves for cooling connections .
--
Oil separator for cooling connections with maximum equivalent length of the cooling line greater than 50 metres .
--
Position of air supply of the outdoor unit : side or upper .
--
Different configurations of available pressure from 7 to 35 mm . w . c
--
Air coil protection grille ( it ’ s not compatible with the air filter ).
--
Gravimetric filters in the return air . The filters frame is removable , and upon request , it is possible to supply the frame separately with the unit 38NZ / NF , to be joined on site ( width = 53 mm )
■■
Acoustic --
Acoustic insulating cover for compressor
■■
Electric panel --
Electrical power supply with neutral .
--
Energy meter for monitoring of the power consumption of the installation ( with CARRIERrtc control ). Available if the unit does not incorporate electrical heaters .