AHI Carrier Catalog | Page 792

Electrical heater (option) Electric heater assembly in 1 stage. For 2 stages, it is necessary to check if it is possible and the price. Important: with this option, the air fl ow controller is included. Avalaible capacities 40HB/HF Power supply 400 V / III ph / 50 Hz Power output kW 3 6 9 12 15 18 80 / 90 Current A 4,3 8,7 13 17,3 - - 120 / 160 Current A 4,3 8,7 13 17,3 21,7 26 Frame for assembly of the electrical heater on fan supply 40HB/HF 80 / 90 120 160 Power output (kW) Dimensions (mm) A B C 3 a 6 kW (1 row) 150 432 341 9 a 12 kW (2 rows) 262 432 341 3 a 6 kW (1 row) 150 432 341 9 a 12 kW (2 rows) 262 432 341 12 a 18 kW (2 rows) 262 482 443 3 a 12 kW (1 row) 150 547 443 15 a 18 kW (2 rows) 262 547 443 Note: This frame is designed with side access for maintenance purposes. Auxiliary Hot Water Coil (Optional) Two-row hot water coils for mounting in duct 40HB/HF AIR TREATMENT Nominal air flow m3/h Air pressure drop Water 80/60ºC Water 90/70ºC Weight (empty) 90 120 160 4.000 4.600 6.000 7.000 mm.w.c 3,6 4,5 3,4 4,4 Heating capacity kW 34,7 37,7 52,7 57,9 Water flow m3/h 1,5 1,6 2,3 2,5 Water pressure drop m.w.c 1,0 1,2 1,2 1,4 Heating capacity kW 42,8 46,6 65,0 71,4 Water flow m3/h 1,8 2,0 2,8 3,1 Water pressure drop m.w.c 1,5 1,7 1,8 2,1 kg 9,5 9,5 13,5 13,5 1 1/4” 1 1/4” 1 1/2” 1 1/2” Diameter of hydraulic connections 792 80 C A R R I E R 2 0 1 6 / 2 0 1 7