AHI Carrier Catalog | Page 790

Physical Data 40HB/HF 80 90 120 160 Indoor circuit centrifugal fan Nominal air flow m3/h 4.000 4.600 6.000 7.000 Available static pressure mm.w.c 20 20 20 20 Number / turbines 1/1 Motor output kW 1,5 2,2 2,2 2,2 Power input kW 1,07 1,48 1,56 1,62 Speed r.p.m. 1.497 1.613 1.219 1.030 A 3,6 5,0 5,0 5,0 Length mm 1.500 1.500 1.831 1.831 Width mm 870 870 1.103 1.103 Height mm 639 639 706 706 Weight kg 125 128 171 181 Max. abs.current Fan Dimensions Additional load of R-410A refrigerant Aditional load per linear metre of piping for equivalent maximum lengths exceeding 7 metres: Nominal diameter inches 1/4” 3/8” 1/2” 5/8” 3/4” 7/8” 1” 1 1/8” Interior section cm 0,149 0,444 0,900 1,505 2,282 3,120 4,290 5,346 Liquid line charge g/m 19,3 57,0 115,0 193,5 292,3 404,1 550,3 685,7 Gas line charge g/m - 0,2 0,4 0,7 1,0 1,4 2,0 2,5 2 Power level and sound pressure level dB(A) AIR TREATMENT A) The sound power level in the outdoor unit fan supply to be taken into account for the silencer operation: 38HB/HF 80 90 120 160 dB(A) 79.1 81.5 79.2 83.9 B) The sound pressure level of the outdoor unit, measured at a distance of 5 metres, in open fi eld, directivity at 2 and 1.5 m from the ground, is: 38HB/HF 80 90 120 160 dB(A) 65.0 68.4 68.5 69.7 C) The sound pressure level of the indoor unit, with the ducted supply and discharge connections, measured at a distance of 5 metres, in open fi eld, directivity at 2 and 1.5 metres from the ground, is: 40HB/HF 80 90 120 160 dB(A) 65.9 64.6 65.2 64.2 Note: The sound pressure level depends on the installation conditions and, as such, is only indicated as a guide. 790 C A R R I E R 2 0 1 6 / 2 0 1 7