SPLIT-SYSTEM COOLING UNITS AND HEAT PUMPS
38HB/HF & 40HB/HF
Physical Data
38HB/HF
80
90
120
160
Cooling
Cooling capacity (1)
kW
19,3
21,2
27,3
36,9
Power input (3)
kW
8,0
9,6
11,5
14,2
2,40
2,20
2,38
2,60
22,3
24,2
32,0
41,9
EER performance
Heating
Heating capacity (2)
kW
Power input
kW
(3)
COP performance
7,7
9,1
10,6
13,5
2,88
2,67
3,03
3,11
Outdoor circuit centrifugal fan
Nominal air flow
m3/h
6.500
7.000
10.000
12.200
Available static pressure
mm.w.c
25
20
20
20
kW
3
3
4
5,5
Number / turbines
1/1
Motor output
Power input
kW
2,33
2,71
2,51
3,18
Speed
r.p.m.
1.489
1.522
940
836
Compressor
Type
Scroll
No. compressors / circuits / stages
1/1
Oil type
Copeland 3MAF 32 cST, Danfoss POE 160 SZ, ICI Emkarate RL32 CF, Mobil
EAL Artic 22 CC
Volume of oil
l
1,6
3,0
3,3
3,3
Liquid line
1/2"
1/2"
5/8"
5/8"
Gas line
7/8"
7/8"
1 1/8"
1 1/8"
Cooling connections
Refrigerant
R-410A
GWP
Global warming potential (4)
2.088
Load up to 7,5 m
kg
6,5
6,6
7,8
10,2
Environment impact
tCO2 e
13,6
13,8
16,3
21,3
20,1
25,1
AIR TREATMENT
Type
Electrical features
Mains voltage
400 V / III ph / 50 Hz (±10%)
Power supply
3 Wires + GND
Maximum absorbed current
Compressor
15,9
A
15,3
Fan
A
6,9
6,9
9,0
11,6
Control
A
0,9
0,9
0,9
0, 9
Total
A
23,7
23,1
30,0
37,6
mm
1.680
1.680
2.088
2.088
Length
(1)
(2)
(3)
(4)
C
Width
mm
915
915
1.198
1.198
Height
mm
670
670
810
810
Weight
kg
224
245
322
344
CONTROLS
Dimensions
Cooling capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 27ºC (19ºC WB) and 35ºC outdoor temperature.
Heating capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 20ºC and 6ºC WB outdoor temperature.
Total power input by compressors and motorised fans under nominal conditions, calculated in accordance with the EN-14511-2013 standard.
Climatic warming potential of a kilogram of fl uorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years.
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
789