AHI Carrier Catalog | Page 78

The 30PA control is basically comprised of a µPC SMALL control board, a pGD1 graphic terminal, a TCO user terminal (optional for remote control) and sensors. This control allows the connection to a centralised technical management system by using a specific BMS card for some of the following communication protocols: Carel, Modbus, LonWorks®, BACnetTM MSTP, Konnex, Modbus TCP/IP, BACnetTM Ethernet, TCP/IP, SNMP V1-2-3, FTP and HTTP. ■■ pGD1 terminal ■■ Main functions: -- Control in COOLING mode. -- Selection of inlet water temperature setpoints for COOLING mode. -- Permanent control and optimization of the operating parameters -- Safety management. -- Timing of the compressor. -- Control of condensation and evaporation pressures. -- Control of outdoor electronic plug-fan (HEE version). -- Control of the circulation pump. -- Regulation of the water outlet temperature. -- Compensation of the setpoint based on the outdoor temperature. -- Timer and weekly programming. -- Failure diagnosis and main alarm. This graphic terminal, installed on the electric panel of the machine, allows: -- The initial programming of the unit -- Modification of operating parameters. -- Unit ON / OFF. -- Selection of the operating mode. -- Setting of setpoints. -- On-screen display of controlled variables and sensor values measured. -- On-screen display of active alarms and historical record of alarms. ■■ TCO user terminal (optional for remote control): The TCO user terminal, for remote control, allows: -- Modification of some operating parameters. -- Unit ON / OFF. -- Selection of the operating mode and setting of setpoints. -- On-screen display some controlled variables and probe values. -- On-screen display of alarms codes. Cooling mode Air 30PA/PAC * ** Water (outlet T.) Max. Min. Max. Min. 46ºC 12ºC * 18ºC 5ºC ** +46 +12 Condensation pressure control Series Outdoor temperature °C DB Operation limits Outdoor temperature °C DB COOLING Controls With control of the condensation pressure operating up to -15ºC. Minimum outlet temperature. With the option of glycol water for lower temperature operation from 5ºC to -10ºC. -15 +20 +10 +0 -10 -15 Mandatory glycol -10 0 +5 +18 Outlet water temp. in the evaporator °C 78 C A R R I E R 2 0 1 6 / 2 0 +30 Outlet water temp 1 7