Installation
UNDER installation: reversed air supply
OVER installation: top air supply
Installation 1
Installation 3
Installation 4
Assembly 5
Air Supply via raised floor
Front return
Rear return
Return air belmow
Features and advantages
■■ Casing
AIR TREATMENT
-- Double-wall construction
-- RAL 7035 grey pre-lacquered panel, removable:
• 1 mm pre-lacquered exterior panels,
• Glass wool, thickness 25 mm, class M0,
• 0.8 mm galvanised interior panels
■■ Filtration
-- F2SI type filter cells, efficiency 90 % as per ASHRAE
gravimetric test (G 4)
-- Optional F7 opacimetric filtration
-- Optional dual filtration (G4+F7)*
-- Filter cells tightly compressed against counter-frame
by a gasket to ensure a completely leaktight seal
-- Fouling level monitored by an analogue pressure
sensor
■■ Cooling coil cross-section
-- Coil made of copper tubes, aluminium fins
-- Condensate drain pan
-- Model W with 2- or 4-way control valve fitted and
connected. Optional thermally insulated flexible
connections
■■ Ventilation section
-----
Direct coupling centrifugal fan
Three-phase 400V electric motor, 4 poles, class F
Frequency inverter fitted for air flow rate control
Air flow rate monitored by an analogue pressure
sensor
■■ Electrics box
------------
Electrical power and control box consisting of:
Power supply: three-phase 400 V/50 Hz + E
Emergency stop master switch
Protected transformer (three-phase, 400/24 V)
Protection and control of fan motor, and of humidifier
and electric heater depending on options selected
Regulated by Carrier CCU Controller
Return air dry-bulb temperature control
Return humidity control, in supply or dehumidification
mode (optional)
Options available: water leak detection, fire thermostat
and supply air low-limit monitoring
Remote control and fault summary contact
Condensate drain pump (optional)
* except for models W 5/8/12