FRESH AIR UNITS WITH ENERGY RECOVERY
39SQC/R/P
Model 39
SQR 0909 SQR 1010 SQR 1111 SQR 1212 SQR 1412 SQR 1416
SQP 0909 SQP 1010
Power circuit
Built-in main disconnect switch
Nominal power supply
V-ph-Hz
400-3-50 neutral
Voltage range
V
360-440
Maximum unit power
kW
11.75
15.75
22.75
22.75
22.75
30.75
Maximum supply cable size
mm2
6
10
16
16
16
25
Main switch
A
40
63
63
63
63
80
Short circuit unit capacity
kA
15
15
15
15
15
15
Recommended power line fuse protection
A
35
50
63
63
63
80
Control circuit power
Built-in 24 V control transformer
Note: Electric pre-heater and reheater have separate power supply.
CONTROLS
AIR TREATMENT
Hospital exhaust and supply units with run-around coil for energy recovery
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
731