AHI Carrier Catalog | Page 73

DUCTABLE AIR-COOLED SCROLL CHILLERS 30PA / PAC STD version: Technical characteristics 30PA 90STD 100STD 120STD 160STD 180STD Cooling 17,00 21,10 25,20 32,70 36,00 7,75 9,15 10,00 12,60 14,40 (m3/h) Net efficiency EER 2,29 2,31 2,51 2,60 2,49 Seasonal efficiency Nominal air flow ESEER *** 2,61 6500 2,59 7000 2,81 10000 2,94 12200 2,85 12200 Available static pressure (mm.w.c) 20 Compressor kW 2,2 2,2 3,0 4,0 4,0 Power input **** kW 1,46 1,77 2,33 2,83 2,83 Speed (r.p.m.) 973 1027 837 734 734 Nominal water flow (m3/h) 3,1 3,7 4,3 5,7 6,2 Pressure drop (m.w.c) 2,3 3,2 2,9 4,7 2,9 Minimum water flow (m3/h) 2,2 2,7 3,1 4,1 4,3 Maximum water flow (m3/h) 6,2 7,4 8,8 11,3 12,7 Type of hydraulic connections Gas threaded Diameter of connections 1 1/4" M Type Scroll Number of compressors / stages / circuits 1/1/1 Oil type Copeland 3MAF 32 cST, Danfoss POE 160 SZ, ICI Emkarate RL 32 CF, Mobil EAL Artic 22 CC 3,0 3,3 3,3 3,3 6,2 Volume of oil Refrigerant l Type 2.088 Charge kg 5,9 6,1 6,6 6,9 7,6 Environment impact (tCO2e) 12,3 12,7 13,8 14,4 15,9 Electrical power supply 400 V / III ph / 50 Hz (±10%) Power supply 3 Wires + Ground + Neutral Maximum absorbed Compressor current Fan Dimensions Weight 1 1/2" M R-410A Global warming potential (GWP) ***** Electrical characteristics COOLING Indoor circuit 1 Motor output HEATING HEATING Number / turbines A 15,2 17,3 20,5 25,4 30,5 A 5,0 5,0 6,9 8,9 8,9 Control A 0,9 0,9 0,9 0,9 0,9 Total A 21,1 23,2 28,3 35,2 40,3 Length mm 1117 1398 Width mm 860 860 Height mm 1447 Empty kg 302 310 372 390 388 In operation kg 306 315 379 397 396 90STD 100STD 120STD 160STD 180STD 3,22 4,5 2,5 3,17 5,4 3,5 3,02 6,2 4,6 386 408 2113 860 1447 469 497 476 503 30PAC 1727 Cooling Seasonal efficiency Indoor circuit Expansion vessel Dimensions Weight ESEER Nominal water flow Pressure drop Volume Filled pressure (m3/h) (m.w.c) l kg/cm2 2,95 3,2 2,3 12 1,5 3,00 3,7 3,1 Length Width Height Empty In operation mm mm mm kg kg 1117 860 1447 310 327 1398 860 1727 370 390 * Cooling capacity calculated in accordance with the EN-14511-2013 standard given for outlet water temperature conditions of 7ºC and 35ºC outdoor temperature. ** Total power input by compressor, motorised fan and electronic control under nominal conditions, calculated in accordance with the EN-14511-2013 standard. Options are not included. *** European Seasonal Energy Efficiency Ratio (ESEER) obtained in accordance with the calculation conditions established by the certification body EUROVENT. **** Energy-efficient motors IE2. ***** Climatic warming potential of a kilogram of fluorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years. C A R R I E R 2 0 1 6 / 2 0 1 7 73 AIR TREATMENT Outdoor circuit centrifugal-fan kW kW CONTROLS Cooling capacities Net cooling capacity * Net power input **