AIR TREATMENT
■■ Hydraulic coil
-- Copper pipes, aluminium fins
-- Coil can be integrated or additional (cased)
-- With the accessory fitted, 2 or 3-way control valve
and 0-10V actuator controlled by 39HX Control for
setpoint accuracy
-- Galvanised steel condensate drain pan (cooling coil or
mixed coil only)
■■ Electric box
Electric box for power, control and internal regulation of the
unit, comprising as standard:
-- Power supply (3-Ph/400 V/Earth or 1-Ph/230 V/Earth).
-- Main disconnect switch
-- Protected transformer
-- Protection and control of all electrical components by
a circuit-breaker and a contact switch
-- Peripheral options and power terminal block
-- Control by factory pre-programmed CAREL pCO3 PLC
-- Hand-held cabled micro-terminal
-- Fault summary contact
-- 3 temperature sensors
-- 4 pressure sensors
■■ Electric heaters
-- High-limit safety thermostat with automatic and
manual reset
-- Control by 2-stage on/off operation fully controlled by
39HX Control
■■ Accessories
-- Damper with airfoil blades driven by an on/off
spring-return actuator
-- Flexible sleeve
-- Adjustable feet
-- CO2 air quality sensorRoof
-- Canopy
-- Mixing section
-- Indoor environment switch
-- ModBus RTU, LON, KNX, ModBus TCP, BACnet IP
communication card
Models & sizes
Power (kW)
Current (A)
Voltage (V)
C 010 & E 010
V 010
H 070 & H 012
4.5
20
1-Ph 230
V 015 (additional casing)
H 016 (additional casing)
7.20
11
V 015
8.1
12
C 020 & E 020
10.8
16
C 030 & E 030
12.6
19
C 040 & E 040
16.8
25
E 050
19.8
29
C 060 & E 060
22.8
34
E 075
31.2
46
E 100
N/A
N/A
E 150
N/A
N/A
Specifications
Class
Mechanical strength
D2
Airtightness
L2
Filter by-pass leak
F9
Thermal transmission
T3
Thermal bridge
TB2
712
C
A
R
R
3-Ph 400
I
E
R
2
0
1
6
/
2
0
1
7