HIGH-EFFICIENCY DUAL-FLOW AIR HANDLING UNIT
39HX
Range
AHU N° 15.05.006
Range 39HX
Classic 39HXC & 39HXE
Models
Nominal flow rate (m3/h)
Max.* power (kW)
Max current* (A)
Voltage (V)
010
1000
1.43
6.2
1-Ph 230
020
2000
2.50
3.6
030
3000
3.82
5.5
040
4000
4.23
6.1
050
5000
4.23
6.1
060
6000
6.03
8.7
3-Ph 400
075
7500
6.03
8.7
100
10000
12.06
17.4
150
15000
15.45
22.3
Models
Nominal flow rate (m3/h)
Max.* power (kW)
Max current* (A)
Voltage (V)
010
1000
1.43
6.2
1-Ph 230
015
1500
2.50
3.6
020
2000
2.50
3.6
Vertical 39HXV
3-Ph 400
Ceiling-mounted 39HXH
Nominal flow rate (m3/h)
Max.* power (kW)
Max current* (A)
007
700
1.43
6.2
012
1200
1.43
6.2
016
1600
2.50
3.6
Voltage (V)
1-Ph 230
3-Ph 400
These values are given as a guide for a dual-flow unit fitted as standard, without standard option (electric heater).
Description
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
■■ Heat recovery units
Depending on its arrangement, two different highly energyefficient heat recovery systems are available:
-- Counter-flow plate heat exchanger with motorised
partial by-pass (H, V and C models)
é Efficiency greater than 80% across the range of air
flows.
-- Rotary heat exchanger equipped with speed control
(E model)
é Efficiency greater than 80% at nominal flow rate.
CONTROLS
■■ Casing
-- Double-skin panels made from steel sheets, galvanised
on both sides, thickness 8/10 mm
-- RAL 7035 grey lacquer coating finish on external panels
-- M0/A1 fire rating
-- Mineral wool, thickness 50 mm
■■ Filtration
-- M5 HEE, F7 HEE, F9 HEE filters
-- Filter cells kept compressed by a special system to
ensure a leaktight seal
-- Filter fouling value monitored by analogue sensor and
displayed by controller
■■ Ventilation
-- Plug fan driven by an electronically commutated motor
with built-in speed control
AIR TREATMENT
*
Models
711