AHI Carrier Catalog | Page 671

INDIVIDUAL COMFORT MODULES  42BJ Physical and electrical data 42BJ ICM LEC 1.9 Fan speed* L M H L M H L M H l/s 16 145 201 24 160 223 28 148 204 m3/h 56 521 722 88 575 803 101 534 733 Pa 1 50 97 1 50 99 3 50 92 Total cooling capacity kW 0.45 2.99 3.74 0.66 3.95 5.26 1.12 3.94 4.91 Sensible cooling capacity kW 0.36 2.34 3.00 0.46 2.91 3.95 0.75 2.78 3.53 Water flow rate l/s 0.02 0.12 0.17 0.03 0.19 0.25 0.06 0.25 0.26 l/h 80 448 628 118 699 912 224 884 935 Water pressure drop kPa 2 27 47 2 39 61 5 61 68 Water content l 0.9 0.9 0.9 1.2 1.2 1.2 1.5 1.5 1.5 kW 0.51 3.56 4.45 0.75 4.72 6.33 1.19 4.53 5.77 Air flow Available static pressure 2.9 4.9 Cooling mode** Two-pipe heating mode*** Heating capacity Four-pipe heating mode**** Heating capacity kW 0.62 3.12 3.70 1.08 4.30 5.18 1.87 5.47 6.54 Water flow rate l/s 0.02 0.07 0.10 0.03 0.10 0.12 0.05 0.15 0.16 l/h 60 267 348 94 376 449 168 550 577 Water pressure drop kPa 1 15 23 4 32 41 8 67 73 Water content l 0.2 0.2 0.2 0.29 0.29 0.29 0.45 0.45 0.45 Electric heater V-ph-Hz 230-1-50 Maximum capacity kW 0.5 1.9 2.23 0.75 2.12 2.25 1 2.25 2.25 Maximum current drawn A 11 11 11 11 11 11 11 11 11 Sound power level (return + radiated) dB(A) 29 53 59 34 52 59 32 56 61 Sound power level (supply) dB(A) 26 59 66 20 63 69 31 65 72 Global sound power level dB(A) 31 61 67 34 63 69 34 65 72 Sound pressure level† dB(A) 10 40 46 13 42 48 13 44 51 NR value† - 35 41 - 37 43 - 39 46 Electrical data, motor 230 V-1 ph-50 Hz, EC motor with low energy consumption 46 186 Sound levels 49 160 4 68 174 5 Power input W 4 Air filter F5 or F6 mm 240 x 400 240 x 550 315 x 550 in 1/2 gas 1/2 gas 1/2 gas Connection diameter, chilled and hot-water coil mm 200 200 250 mm 900 1100 1100 Depth mm 665 815 815 Height mm 270 270 345 Unit weight (standard) kg 31 40 50 Fan speed: L = Low, M = Medium, H = High Eurovent conditions: Entering air temperature 27°C/47% rh, entering water temperature 7°C, water temperature difference 5 K. Eurovent conditions: Entering air temperature 20°C - entering water temperature 50°C, with same water flow rate as in cooling mode. Eurovent conditions: Entering air temperature 20°C - entering water temperature 70°C, water temperature difference 10 K. Based on a hypothetical sound attenuation for the room and the system of -21 dB(A). CONTROLS * ** *** **** † Spigot connection diameter Length AIR TREATMENT Physical data C A R R I E R 2 0 1 6 / 2 0 1 7 671