Operating limits
Cooling mode
Heating mode
Water circuit
Min. inlet Temperature > 5°C
< 40% ethylene / propylene glycol
Water side pressure < 15.5 bar (1550 kPa)
Ambient temperature and humidity T < 27°C / 65% relative humidity
or Humidity weight < 14.7 g/kg dry air
Supply air temperature
T > 12°C with maximum ambient humidity
conditions (14.7 g/kg dry air)
EC Motor - Electrical input
Max. inlet Temperature < 80°C
< 40% ethylene / propylene glycol Water side
pressure < 15.5 bar (1550 kPa)
T < 40°C
T < 60°C with supply plenum and spigots
application
Recommandation to avoid stratification T < 35°C
Min: 216V
Max: 244 V
60 or 50 Hz -1ph
Min: 207V
Max: 253 V
60 or 50 Hz -1ph
(60Hz not available for 42NH325 & 335)
Min: 216V
Min: 216V
60 or 50 Hz -1ph
Min: 207V
Max: 253 V
60 or 50 Hz -1ph
(60Hz not available for 42NH325 & 335)
AC motor - Electrical input
NOTE: All performances data certified by Eurovent are based on 50Hz application.
Carrier doesn’t ensure the same performances when the unit operates at 60Hz; the RPM and power input of the fan-motor are usually higher.
Dimensional drawings
NOTE: All drawings shown have the coil connections on the right-hand side. Units with left-hand connections are symmetrical.
AIR TREATMENT