AHI Carrier Catalog | Page 662

Functions and configurations Standard spigots configuration Large and small plenums for inlet and outlet are available for all sizes according to the drawings below: LARGE INLET OR OUTLET COMPACT INLET OR OUTLET AIR TREATMENT COMPACT INLET OR OUTLET LARGE INLET OR OUTLET 42NH & 42NL Size 2xx LIMITS (*) 42NH & 42NL Size 4xx 42NH & 42NL Size 3xx 4x DN 160 4x DN 160 5x DN 160 3x DN 160 4x DN 260 4x DN 200 2x DN 160 2x DN 160 3x DN 160 1x DN 160 2x DN 200 2x DN 200 MIN. SPIGOTS. = 1x160 or 1x200 (2x160 and 1x200 for 42NH279) MIN. SPIGOTS. = 2x160 or 1x200 (2x160 and 2x200 for 42NL range) MIN. SPIGOTS. = 3x160 or 2x200 42NH & 42NL Size 5xx 42NH & 42NL Size 6xx 42NH & 42NL Size 7xx 6x DN 160 6x DN 200 5x DN 200 6x DN 200 4x DN 200 5x DN 250 3x DN 200 4x DN 200 2x DN 250 3x DN 250 4x DN 160 3x DN 120 MIN. SPIGOTS. =3x160 or 2x200 (24x160 and 3x200 for 42NL range) MIN. SPIGOTS. = 4x200 or 3x250 MIN. SPIGOTS. = 3x200 or 2x200 (*) = Minimum number of spigots required to ensure sufficient available static pressure and fan reliability NOTE: • Electrical heater are not available for 42NL Units when plenum are selected (due to minimum airflow requirement) • Non-standard configurations not listed above can be provided upon special request. Contact your local Carrier representative. 662 C A R R I E R 2 0 1 6 / 2 0 1 7