AHI Carrier Catalog | Page 633

ROOM FAN COIL UNITS  42N Four-way valve pressure drop 100 2 1 3 4 Pressure drop, kPa 10 1 0,1 0,01 0,10 1,00 Water flow, l/s 1 2 3 4 1/2" bypass, cold and hot 1/2" open, cold and hot 3/4" bypass 3/4" open Notes: Pressure drop values are based on a water temperature of 20°C. For other water temperature values, use a correction factor of 0.4% per °C. Air throw 42N 42N_S 15-E 19 42N_S 15-E 19 Two-pipe Four-pipe 42N_S 20-E 29 42N_S 26 S 15-S 20-S 30-S 45 E 19-E 29-E 39-E 49-E 69 S 26-S 42-S 65 m l/s m3/h m l/s m3/h m l/s m3/h m l/s m3/h Speed 5 - 0.4 35.8 129 0.4 35.4 127 0.9 59.1 213 - - - Speed 4 - 1.7 55.6 200 1.7 56.2 202 1.8 79.8 287 - - - Speed 3 Speed 3 2.3 69.4 250 2.3 69.2 249 2.2 91.9 331 2.2 93.0 335 Speed 2 Speed 2 2.8 83.6 301 2.8 84.6 304 2.7 107.4 387 3.6 148.9 536 Speed 1 Speed 1 3.2 97.2 350 3.2 97.8 352 3.2 127.6 459 4.4 190.3 685 42N 42N_S 30-E 39 42N_S 42 42N_S 45-E 49 42N_S 65-E 69 S 15-S 20-S 30-S 45 E 19-E 29-E 39-E 49-E 69 S 26-S 42-S 65 m l/s m3/h m l/s m3/h m l/s m3/h m l/s m3/h Speed 5 - 0.5 97.1 350 - - - 0.8 145.6 524 0.8 145.6 524 Speed 4 - 2.1 126.0 454 - - - 2.9 185.3 667 2.9 185.3 667 Speed 3 Speed 3 3.2 153.2 552 3.0 147.5 531 4.6 223.6 805 5.1 236.9 853 Speed 2 Speed 2 4.3 181.8 654 5.4 221.7 798 6.4 276.7 996 8.0 330.8 1191 Speed 1 Speed 1 5.0 207.2 746 6.6 268.0 965 8.1 332.6 1197 10.2 421.9 1519 C A R R I E R 2 0 1 6 / 2 0 1 7 633 AIR TREATMENT The air throw value gives the position where the air velocity is 0.2 m/s when the air is blown horizontally with the grille pointing upwards. Air throw values are given as a guideline only, and change with room dimensions and furniture used in the room. CONTROLS