AHI Carrier Catalog | Page 623
ROOM FAN COIL UNITS 42N
Units with LEC motors, two and four-pipe coils
42N_, 2-pipe coil
Fan speed
E19
%
100
l/s
96
m3/h
345
Fan type
E29
80
60
40
20
100
82
69
55
34
126
106
296
247
198
123
453
382
One, tangential
Air flow
E39
80
60
40
20
100
91
79
59
205
181
327
283
214
739
651
One, centrifugal
80
60
40
20
152
126
97
547
454
349
Two, centrifugal
Cooling mode*
kW
1.2
1,09
0,97
0,83
0,58
2,13
2,01
1,78
1,54
1,15
3,68
3,34
2,91
2,45
1,92
Sensible cooling capacity kW
Total cooling capacity
1,1
1,01
0,89
0,74
0,5
1,77
1,62
1,42
1,23
0,93
3,04
2,73
2,35
1,97
1,4
Water flow rate
l/s
0,06
0,05
0,05
0,04
0,03
0,1
0,09
0,09
0,07
0,06
0,18
0,16
0,14
0,12
0,09
l/h
210
190
170
140
100
370
340
310
260
200
630
570
500
420
330
m3/h
0,21
0,19
0,17
0,14
0,1
0,37
0,34
0,31
0,26
0,2
0,63
0,57
0,5
0,42
0,33
Water pressure drop
kPa
12
10
8
6
3
5
5
4
3
2
16
14
11
8
5
Water content
l
Heating mode**
Heating capacity
kW
1,87
1,74
1,48
1,29
0,88
3,01
2,72
2,36
2,05
1,59
4,77
4,33
3,78
3,25
2,62
Water pressure drop
kPa
10
8
7
5
3
4
4
3
2
1
13
11
8
6
4
Water content
l
0.6
1.4
1.8
Sound levels
Sound power level
dB(A)
52
47
43
37
29
52
46
43
37
32
56
51
47
42
36
Sound pressure level***
dB(A)
43
38
34
28
20
43
37
34
28
23
47
42
38
33
27
39
34
29
23
16
36
32
29
22
15
41
37
33
28
22
NR Value
Electrical data
Power input
W
14
10
7
4
3
17
12
8
4
3
39
26
17
11
6
Current drawn
A
0.15
0,14
0,13
0,12
0,1
0.16
0,13
0,12
0,11
0,1
0.29
0.21
0.16
0.12
0.1
W
800
Electric heater
10 00
2000
Current drawn
A
3.48
4.35
8.7
High capacity
W
500
500
1000
Current drawn
A
2.18
2.18
4.35
E/E
A/A
E/E
3/4 gas
3/4 gas
3/4 gas
Eurovent energy class
FCEER/FCCOP
Connection diameter
Eurovent conditions: Entering air temperature = 27°C db/19°C wb – entering/leaving water temperature = 7°C/12°C, high fan speed.
Eurovent conditions: Entering air temperature = 20°C, entering water temperature = 50°C, same water flow rate as in cooling mode.
Based on a hypothetical acoustic attenuation for the room and the air distribution system of -9 dB(A).
This unit complies with all applicable standards for EC marking (for further details see Declaration of Conformity). Except the unit size 42N_S65 which is not CE labeled due to fan
efficiency regulation 327/2011 but is fully compliant with Machinery (2006/42/EC) and Electromagnetic Compatibility (2004/108/EC) directives.
CONTROLS
*
**
***
†
in
AIR TREATMENT
High capacity
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1