Physical Data
«Cold shower» system
The one-way 180° diffuser is fitted with an «anti cold shower»
system that maximises comfort by preventing cold air from
falling between two cassettes.
The system incorporates two deflectors in the insulation
which offsets the air stream slightly in the lateral axis. When
the units are placed side by side in the same room, the air
flows do not oppose one another and cross over in parallel,
which avoids any cold air draughts.
This patented system removes the discomfort caused by
draughts without having to reduce the outlets and with
no increased noise levels, while maintaining the air flow
necessary for the thermal requirements.
With anti «cold shower» system
Without anti «cold shower» system
42KY Unit performance
AIR TREATMENT
4Tubes
42KY
20D
Speed
HS
29D
MS
LS
HS
30D
MS
LS
39D
HS
MS
LS
HS
MS
LS
Voltage
V
-
-
-
4.9
4.2
2.5
-
-
-
5.3
4.6
3
Input Power
W
45
41
34
17
12
5
77
56
40
21
15
6
Air Flow Rate
m3/h
420
355
215
420
355
215
655
520
405
520
455
290
Heating Capacity
Pressure drop
W
2820
2580
2020
2830
2600
2040
3460
3000
2600
2820
2610
2110
kPa
21
18
12
21
18
12
28
22
17
25
22
15
Cooling Capacity
Total
W
2090
1910
1450
2060
1880
1420
3790
3140
2570
2910
2620
1920
Sensible
W
1840
1620
1120
1810
1600
1090
3040
2470
1980
2280
2020
1410
Pressure drop
kPa
10
8
5
10
8
5
19
13
9
13
11
6
Lw
dB(A)
51
47
35
51
47