AHI Carrier Catalog | Page 611
ONE-WAY COANDA EFFECT CASSETTE 42KY
Physical Data
42KY Unit performance
2Tubes
42KY
10C
Speed
19C
20C
HS
MS
LS
HS
MS
LS
HS
MS
LS
-
-
-
4.9
3.9
2.5
-
-
-
Voltage
V
Input Power
W
45
41
34
17
8
5
45
41
34
Air Flow Rate
m3/h
440
375
230
440
305
230
420
355
215
Heating Capacity
Pressure drop
W
2410
2180
1640
2420
1930
1650
3270
2860
1930
kPa
9
8
5
9
6
5
16
13
7
W
1740
1570
1220
1720
1380
1190
2640
2320
1610
Cooling Capacity
Total
Sensible
W
1590
1430
1060
1570
1230
1040
2070
1790
1180
Pressure drop
kPa
11
9
6
11
7
5
19
15
8
Lw
dB(A)
49
46
37
49
42
37
51
47
35
LP
dB(A)
37
34
25
37
30
25
39
35
23
32
29
19
32
25
19
34
30
18
NR
Eurovent FCEER
Class
F
A
E
Eurovent FCCOP
Class
F
A
E
42KY
29C
30C
39C
Speed
HS
MS
LS
HS
MS
LS
HS
MS
LS
3
Voltage
V
4.9
4.2
2.5
-
-
-
6.7
5.3
Input Power
W
17
12
5
77
56
40
38
21
6
Air Flow Rate
m3/h
420
355
215
655
520
405
655
520
290
W
3290
2880
1960
5070
4090
3240
5100
4120
2500
kPa
16
13
6
25
17
12
25
17
7
Pressure drop
Cooling Capacity
Total
W
2610
2290
1580
4420
3600
2880
4390
3560
2220
Sensible
W
2040
1770
1150
3340
2680
2110
3310
2650
1580
Pressure drop
kPa
18
15
7
30
20
13
29
20
9
Lw
dB(A)
51
47
35
58
51
45
58
51
40
LP
dB(A)
39
35
23
46
39
33
46
39
28
34
30
18
40
34
27
40
34
21
Class
Class
A
A
NR
Eurovent FCEER
Eurovent FCCOP
D
D
A
A
AIR TREATMENT
Heating Capacity
CONTROLS
EUROVENT conditions
Cooling mode: (2 tubes): Air inlet temperature: 27°C/19°CBH, Water inlet/outlet temperature: 7°C/12°C
Heating mode: (2 tubes ): Air inlet Temperature: 20°C, water inlet temperature: 50°C, water flow rate identical to cold mode
The sound pressure levels and NR levels are based on hypothetical attenuation of the room of -12dB(A).
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
611