AHI Carrier Catalog | Page 598

42GW
200
300
400
Coil type
4 pipes
4 pipes
4 pipes
Fan speed *
1
2
3
1
2
3
1
2
3
Air flow
l / s
183
125
100
204
140
89
249
173
134
Cooling mode Total cooling capacity
kW
2
1,5
1,3
3,4
2,7
2
4,05
3,24
2,57
Sensible cooling capacity
kW
1,87
1,4
1,19
2,68
2,09
1,5
3,35
2,61
2,05
Water flow rate
l / s
0,1
0,07
0,06
0.17
0.13
0.10
0.20
0.16
0.12
l / h
350
260
230
580
460
340
700
560
440
Water pressure drop
kPa
13
8
6
11
7
4
15
10
6
Water content
l
0.4
1.1
1.1
Heating mode Heating capacity
kW
1,9
1,44
1,24
6,37
5,1
3,61
6,81
5,81
5,01
Water flow rate
l / s
0,05
0,04
0,03
0.15
0.12
0.09
0.16
0.14
0.12
l / h
170
130
110
548
439
310
585
499
430
Water pressure drop
kPa
35
21
16
25
17
9
29
22
17
Water content
l
0.1
0.6
0.6
Sound power level
dB ( A )
49
40
36
53
44
35
57
48
42
Sound pressure level **
dB ( A )
40
31
27
44
35
26
48
39
33
Power input
W
58
35
25
54
32
16
94
55
35
Current input
A
0.27
0.17
0.12
0.24
0.14
0.07
0.41
0.24
0.16
Eurovent energy class FCEER / FCCOP
E / E
C / B
D / C
AIR TREATMENT
42GW
600
701
Coil type
4 pipes
4 pipes
Fan speed *
1
2
3
1
2
3
Air flow
l / s
321
229
139
402
299
166
Cooling mode Total cooling capacity
kW
6,67
4,99
2,99
7,61
6,06
3,19
Sensible cooling capacity
kW
5,1
3,8
2,25
6,01
4,73
2,4
Water flow rate
l / s
0.32
0.24
0.14
0.39
0.32
0.18
l / h
1140
860
510
1310
1040
550
Water pressure drop
kPa
24
14
5
30
20
6
Water content
l
2.4
2.4
Heating mode Heating capacity
kW
11,5
8,9
6,01
14,61
11,5
7,31
Water flow rate
l / s
0.27
0.21
0.14
0.35
0.27
0.17
l / h
989
765
516
1247
989
628
Water pressure drop
kPa
13
9
4
20
13
6
Water content
l
1.2
1.2
Sound power level
dB ( A )
54
46
38
59
52
40
Sound pressure level **
dB ( A )
45
37
29
50
43
31
Power input
W
88
61
34
125
92
44
Current input
A
0.46
0.27
0.14
0.63
0.41
0.19
Eurovent energy class FCEER / FCCOP
C / B
D / C
Based on Eurovent conditions : Cooling mode ( 2 and 4-pipe coil ): entering air temperature 27 ° C db / 1 9 ° C wb , entering / leaving water temperature 7 / 12 ° C , high fan speed . Heating mode ( 2-pipe coil ): entering air temperature 20 ° C , entering water temperature 50 ° C , high fan speed , water flow rate as cooling mode . Heating mode ( 4-pipe coil ): entering air temperature 20 ° C , entering water temperature 70 ° C , high fan speed , water ∆t = 10 K * Fan speeds : 1 = high , 2 = medium , 3 = low ** Sound pressure level and NR values are based on a hypothetical sound attenuation for the room of -9 dB ( A ).
Note : Electrical heater version is available on all 2-pipe units .
598 C A R R I E R 2 0 1 6 / 2 0 1 7