AHI Carrier Catalog | Page 575

HIGH TEMPERATURE WATER-TO-WATER HEAT PUMPS   61XWH-ZE0301-1501 Physical data 61XWH-ZE 61XWH-ZE0301 61XWH-ZE0501 61XWH-ZE0751 61XWH-ZE1001 61XWH-ZE1501 Heating Heating Capacity (10°C / 75°C) Heating Capacity (30°C / 75°C) Heating Capacity (20°C / 85°C) Heating Capacity (35°C / 85°C) Maximum hot water temperature Nb of Refrigerant Circuit Operating Weight: Length Width Height kW kW kW kW °C Kg mm mm mm 222 410 2 71 419 85 1 2230 2750 950 1600 362 655 439 671 85 1 3250 3100 950 1750 532 974 645 996 85 1 4500 3300 1150 2000 723 1310 879 1342 85 2 7500 4800 1050 2000 1064 1948 1290 1992 85 2 8800 4850 1350 2200 All performances are not compliant with EN14511-3 : 2013. Custom units which are not certified in accordance with AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Using Vapor Compression Cycle Certification Program. Preliminary product data for information only. Final product data will be submitted by Carrier to Eurovent company during 2016. 61XWH-ZE Evaporator Entering temperature at start-up Leaving temperature during operation Entering/leaving temperature difference at full load Condenser Entering temperature at start-up Leaving temperature during operation Entering/leaving temperature difference at full load Maximum 0 to 15°C 2K 50°C 35°C Up to 20K* 20°C 45°C 2K 70 to 85°C Up to 20K* Water box configurations 1, 2 or 3 passes NEW APPLICATIONS COVERING Condenser hot water temperature (°C) AIR TREATMENT * Minimum HEATING Operating range 85 80 85°C 75 70 65 60 CONTROLS Operating map extension under evaluation 45 -5 C A R R I E R 2 0 1 6 / 2 0 1 7 0 5 10 15 20 25 30 35 Evaporator cold water temperature (°C) 575