MEDIUM TEMPERATURE WATER-TO-WATER HEAT PUMPS
30XWHP-ZE/30XWHV-ZE
Physical data
30XWHP
ZE0301
30XWHP
ZE0401
30XWHP
ZE0451
30XWHP
ZE0551
30XWHP
ZE0601
kW
321
449
510
648
695
30XWHP ZE
Heating
Performance Information
Heating Capacity*
kW/kW
6,25
6,72
6,64
6,83
6,63
Maximum hot water temperature
°C
70
70
70
70
Number of Refrigerant Circuit
--
1
1
1
1
70
1
kg
2072/1953
2981/2763
3020/2802
3912/3593
3947/3628
2724/927
/1617
3059/936/
1743
3059/936/
1743
3290/1065/
1950
3290/1070/
1950
Heating Efficiency
COP
Operating/Shipping Weight
Unit Dimensions
LxWxH mm
Electrical Information
Unit Voltage:
V-Ph-Hz 400(+/-10%)
-3-50
400(+/-10%)
-3-50
400(+/-10%)
-3-50
400(+/-10%)
-3-50
400(+/-10%)
-3-50
Standby Power:
kW
0,05
0,05
0,05
0,05
0,05
Power Factor:
--
0,88
0,90
0,90
0,90
0,90
Maximum Current
A
130
176
196
239
263
Start Up Current
A
303
414
414
587
587
Current at Eurovent Conditions
A
87
109
123
146
162
Maximum Current
A
--
--
--
--
--
Start Up Current
A
--
--
--
--
--
Current at Eurovent Conditions
A
--
--
--
--
--
30XWHP
ZE0651
30XWHP
ZE0801
30XWHP
ZE0901
30XWHP
ZE1001
30XWHP
ZE1101
kW
kW/kW
761
6,66
916
6,73
1019
6,79
1165
6,81
1285
6,59
°C
-kg
mm
70
1
3965/3646
3290/1070/
1950
70
2
6872/6218
4795/1039/
1997
70
2
6950/6296
4795/1039/
1997
70
2
7542/6682
4730/1162/
2051
70
2
7752/6892
4730/1162/
2051
V-Ph-Hz 400(+/-10%)
-3-50
kW
0,05
-0,82
400(+/-10%)
-3-50
0,05
0,89
400(+/-10%)
-3-50
0,05
0,90
400(+/-10%)
-3-50
0,05
0,90
400(+/-10%)
-3-50
0,05
0,90
A
A
A
284
587
176
176
414
109
196
414
123
239
587
146
239
587
146
A
A
A
----
176
414
109
196
414
123
196
414
123
239
587
146
Amps (Un)
Circuit 1
30XWHP ZE
HEATING
Circuit 2
Heating
COP
Maximum hot water temperature
Number of Refrigerant Circuit
Operating/Shipping Weight
Unit Dimensions
LxWxH
Electrical Information
Unit Voltage:
Standby Pow er:
Power Factor:
Amps (Un)
Circuit 1
Maximum Current
Start Up Current
Current at Eurovent Conditions
Circuit 2
Maximum Current
Start Up Current
Current at Eurovent Conditions
*
Heating mode conditions: Condenser water heat exchanger, entering/leaving water temperature 30°C/35°C, fouling factor 0 m² K/W. Evaporator water heat exchanger, entering/leaving
water temperature 10°C/7°C, fouling factor 0 m² K/W.
All performances are compliant with EN14511-3 : 2013. Sound power level according to ISO9614-1.
Unit is outside of the scope of AHRI Water-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, but is rated in accordance with AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI).
Preliminary product data for information only. Final product data will be submitted by Carrier to Eurovent company during 2016.
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
571
CONTROLS
Heating Capacity*
Heating Efficiency
AIR TREATMENT
Performance Information