AHI Carrier Catalog | Page 560

Electrical data 30XWHV 580 630 810 880 1150 1280 1470 1570 1710 Power circuit Nominal voltage V-ph-Hz 400-3-50 ± 10% Control circuit supply 24 V, via internal transformer Start-up current* Negligible (lower than maximum current drawn) Maximum power factor * ** *** 0.91-0.93 0.91-0.93 0.91-0.93 0.91-0.93 0.91-0.93 0.91-0.93 0.91-0.93 0.91-0.93 0.91-0.93 Maximum power input, circuit A/B*** kW 155/- 193/- 222/- 246/- 155/155 193/193 222/193 222/222 246/246 Eurovent current draw, circuit A/B** A 175/- 200/- 240/- 265/- 175/175 200/200 240/200 240/240 265/265 Maximum current draw (Un), circuit A/B*** A 270/- 330/- 380/- 421/- 270/270 330/330 380/330 380/380 421/421 Instantaneous start-up current. Eurovent unit operating conditions: evaporator entering/leaving water temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C. Values obtained at operation with maximum unit power input. Values given on the unit name plate. HEATING Options Options No. Description Advantages Use 30XWHV Light-brine solution, down to -3°C 8 Implementation of new algorithms of control to allow chilled brine solution production down to -3°C when ethylene glycol is used (0°C with propylene glycol) Matches with most application requirements for ground-sourced heat pumps and fits with many industrial processes requirements 580-1710 Master/slave operation 58 Unit equipped with supplementary water outlet temperature sensor kit to be fieldinstalled allowing master/slave operation of two units connected in parallel Optimised operation of two chillers connected in parallel with operating time equalisation 580-1710 Single power connection point 81 Unit power connection via one main supply connection Quick and easy installation 1150-1710 Evap. pump power/control circuit 84 Unit equipped with an electrical power and Quick and easy installation: the control of fixed speed pumps is embedded in the control circuit for one pump evaporator unit control side 580-1710 Evaporator dual pumps electrical power / control circuit 84D Unit equipped with an electrical power and Quick and easy installation: the control of fixed speed pumps is embedded in the control circuit for two pumps evaporator unit control side 580-1710 Cond. pump power/control circuit 84R Unit equipped with an electrical power and Quick and easy installation: the control of fixed speed pumps is embedded in the control circuit for one pump condenser unit control side 580-1710 Cond. dual pumps power/control circuit 84T Unit equipped with an electrical power and Quick and easy installation: the control of fixed speed pumps is embedded in the control circuit for two pumps condenser unit control side 580-1710 Condenser insulation 86 Thermal condenser insulation Minimizes thermal dispersions condenser side (key option for heat pump or heat recovery applications) and allows compliancy with special installation criteria (hot parts insulated) 580-1710 Service valve set 92 Liquid line valve (evaporator inlet) and compressor suction line valve Allow isolation of various refrigerant circuit components for simplified service and maintenance 580-1710 Evaporator with one pass less 100C Evaporator with one pass on the water side. Evaporator