AHI Carrier Catalog | Page 559
WATER-TO-WATER HEAT PUMPS 30XWHV 580-1710
Physical data
30XWHV
580
630
810
880
1150
1280
1470
1570
1710
Heating
1932
4
-
1922
4.56
2067
5.34
-
2055
6.27
103
84
4730
1255
2051
7808
110
110
157
10
297
8
3/8
1000
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
AIR TREATMENT
1
1
340
8
3/8
1000
†
Eurovent-certified performances in accordance with standard EN14511-3:2013.
† † Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportionnal heating capacity and power input
generated by the water pump to overcome the internal pressure drop in the heat exchanger.
Condition 1: Cooling mode conditions, evaporator water entering/leaving temperature 12°C/7°C, condenser water entering/leaving temperature 30°C/35°C, evaporator fouling factor 0m².K/W.
Condition 2: Conditions in cooling mode: evaporator water entering/leaving temperature 23°C/18°C, condenser water entering/leaving temperature 30°C/35°C, evaporator/condenser
fouling factor 0m².K/W.
*
In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with
ISO 9614-1 and certified by Eurovent.
** In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from
the sound power level Lw(A).
*** Option 257 = Low noise level.
Eurovent certified data
**** Weight shown is guideline only. Please refer to the unit nameplate.
C
HEATING
106
87
559
CONTROLS
Heating application as per EN14511-3:2013† - standard unit
Condition 1
Heating capacity
kW
649
719
890
974
1261
1428
1594
1761
COP
kW/kW
4.64
4.53
4.56
4.43
4.62
4.61
5
4
Eurovent class heating
A
A
A
B
A
A
Heating application application †† - standard unit
Condition 1
Heating capacity
kW
646
716
887
970
1257
1423
1587
1753
COP
kW/kW
4.84
4.75
4.75
4.63
4.87
4.93
4.92
4.70
Heating application as per EN14511-3:2013† - standard unit
Condition 2
Heating capacity
kW
687
767
956
1021
1335
1524
1712
1898
COP
kW/kW
6.15
5.98
5.96
5.81
6.05
6.00
5.82
5.49
Eurovent class heating
A
A
A
A
A
A
Heating application application †† - standard unit
Condition 2
Heating capacity
kW
685
763
953
1017
1331
1519
1705
1889
6.66
6.33
COP
kW/kW
6.59
6.49
6.39
6.25
6.61
6.72
Sound levels - standard units
Sound power level*
dB(A)
105
105
105
105
106
106
106
106
Sound pressure level at 1 m**
dB(A)
87
87
87
87
87
87
87
87
Sound levels - standard unit + option 257***
Sound power level*
dB(A)
102
102
102
102
103
103
103
103
Sound pressure level at 1 m**
dB(A)
84
84
84
84
84
84
84
84
Dimensions - standard unit
Length
mm
3059
3059
3290
3290
4730
4730
4730
4730
Width
mm
1087
1087
1237
1237
1164
1164
1255
1255
Height
mm
1743
1743
1950
1950
1997
1997
2051
2051
Operating weight****
kg
3152
3190
4157
4161
7322
7398
7574
7770
Compressors
Semi-hermetic 06T screw
compressor, 60 r/s
Circuit A
1
1
1
1
1
1
1
1
Circuit B
1
1
1
1
Refrigerant - standard unit****
R-134a
Circuit A
kg
130
130
180
175
120
120
115
115
120
120
120
115
Circuit B
kg
Global Warming Potential (GWP)
tonnes
186
186
257
250
172
172
172
164
Tonnes of equivalent CO2 of greatest
circuit
Capacity control
Touch Pilot, inverter-driven compressor, electronic expansion valve (EXV)
Minimum capacity
%
20
20
20
20
10
10
10
10
Evaporator
Multi-tube type flooded
Water volume
l
106
106
154
154
297
297
297
297
Water connections (Victaulic)
inch
6
6
8
8
8
8
8
8
Drain and vent connections (NPT)
inch
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Maximum water-side operating pressure kPa
1000
1000
1000
1000
1000
1000
1000
1000
Condenser
Multi-tube type flooded
Net water volume
l
112
112
165
165
340
340
340
340
Water connections (Victaulic)
inch
6
6
8
8
8
8
8
8
Drain and vent connections (NPT)
inch
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Maximum water-side operating pressure kPa
1000
1000
1000
1000
1000
1000
1000
1000
Chassis paint colour
Colour code: RAL7035