AHI Carrier Catalog | Page 553

WATER-COOLED SCREW CHILLERS  30XWH 254-1762 Operating limits Units with option 150 30XW--/30XWH-/30XW-P/30XWHP Minimum Maximum Entering temperature at start-up - 35.0°C Leaving temperature during operation 3.3°C* 15.0°C Entering/leaving temperature difference at full load 2.8 K 11.1 K Entering temperature at start-up 13.0°C** - Leaving temperature during operation 23.0°C** 63.0°C Entering/leaving temperature difference at full load 2.8 K 11.1 K Evaporator Condenser For low-temperature applications, where the leaving water temperature is below 3.3°C, a frost protection solution must be used. Please refer to option 5 and option 6. For lower condenser temperatures, a water flow control valve must be used at the condenser (two or three-way valve). Please refer to option 152 to ensure the correct condensing temperature. Option 150 50 45 40 35 30 25 20 15 0 5 10 15 20 70 65 60 55 HEATING 55 Condenser leaving water temperature, °C Condenser leaving water temperature, °C Standard units 50 45 40 35 30 25 20 0 5 10 15 20 Evaporator leaving water temperature, °C Evaporator leaving water temperature, °C From approx. 45% to full load From approx. 60% to full load Part load limit approx. 35% Part load limit approx. 50% Minimum load limit approx. 15% AIR TREATMENT * ** CONTROLS Minimum load limit approx. 30% C A R R I E R 2 0 1 6 / 2 0 1 7 553