Heating application as per EN14511-3:2013 † - unit with option 150 | |||||||||||
Condition 2 | |||||||||||
Nominal heating capacity |
kW |
958 |
1099 |
1163 |
1294 |
1348 |
1465 |
1583 |
1677 |
1904 |
1975 |
COP |
kW / kW |
4.57 |
4.53 |
4.47 |
4.55 |
4.71 |
4.52 |
4.46 |
4.45 |
4.59 |
4.56 |
Eurovent class heating |
- |
A |
A |
A |
A |
A |
A |
- |
- |
- |
- |
Heating application †† - unit with option 150 | |||||||||||
Condition 2 | |||||||||||
Nominal heating capacity |
kW |
955 |
1094 |
1158 |
1288 |
1344 |
1460 |
1578 |
1672 |
1898 |
1968 |
COP |
kW / kW |
4.86 |
4.83 |
4.79 |
4.91 |
5.02 |
4.82 |
4.80 |
4.86 |
5.02 |
5.03 |
Sound levels - unit with option 150 Sound power level * |
dB ( A ) |
102 |
102 |
102 |
102 |
105 |
105 |
105 |
105 |
105 |
105 |
Sound pressure level at 1 m ** |
dB ( A ) |
84 |
84 |
84 |
84 |
86 |
86 |
86 |
86 |
86 |
86 |
Sound levels - unit with option 257 *** Sound power level * |
dB ( A ) |
100 |
99 |
99 |
99 |
103 |
103 |
103 |
103 |
103 |
103 |
Sound pressure level at 1 m ** |
dB ( A ) |
82 |
80 |
80 |
80 |
84 |
84 |
84 |
84 |
84 |
84 |
Dimensions - unit with option 150 Length |
mm |
2780 |
4025 |
4025 |
4025 |
4730 |
4730 |
4730 |
4730 |
4730 |
4730 |
Width |
mm |
1090 |
1036 |
1036 |
1036 |
1201 |
1201 |
1201 |
1201 |
1947 |
1947 |
Height |
mm |
1920 |
1870 |
1870 |
1925 |
2071 |
2071 |
2071 |
2071 |
1535 |
1535 |
Operating weight **** |
kg |
3672 |
5370 |
5408 |
5698 |
7233 |
7554 |
7622 |
7670 |
9006 |
9032 |
Compressors |
Semi-hermetic 06T screw compressors , 50 r / s |
||||||||||
Circuit A |
- |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
Circuit B |
- |
- |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
Refrigerant **** - standard unit Circuit A |
kg |
140 |
85 |
85 |
105 |
120 |
115 |
110 |
105 |
195 |
195 |
Circuit B |
kg |
- |
85 |
85 |
105 |
120 |
115 |
110 |
105 |
195 |
195 |
Global Warming Potential ( GWP ) Tonnes of equivalent CO 2 of greatest circuit |
tonnes |
200 |
122 |
122 |
150 |
172 |
164 |
157 |
150 |
279 |
279 |
Capacity control |
Touch Pilot , electronic expansion valves ( EXV ) |
||||||||||
Minimum capcity |
% |
15 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
Evaporator |
Multi-pipe flooded type |
||||||||||
Water volume |
l |
98 |
182 |
182 |
205 |
301 |
301 |
301 |
301 |
354 |
354 |
Water connections ( Victaulic ) |
in |
6 |
6 |
6 |
8 |
8 |
8 |
8 |
8 |
8 |
8 |
Drain and vent connections ( NPT ) |
in |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
Max . water-side operating pressure |
kPa |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
Condenser |
Multi-pipe flooded type |
||||||||||
Water volume |
l |
137 |
193 |
193 |
193 |
340 |
340 |
340 |
340 |
426 |
426 |
Water connections ( Victaulic ) |
in |
8 |
8 |
8 |
8 |
8 |
8 |
8 |
8 |
8 |
8 |
Drain and vent connections ( NPT ) |
in |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
3 / 8 |
Max . water-side operating pressure |
kPa |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |