Accessory 00PPG000488000- Heating System Manager type A
■■
Heating System Manager : one heat emitter type with supplementary electric heater or boiler : --
Allows control of a non-reversible heating system that includes a 61WG heat pump and a single heat emitter type or a single comfort zone . For optimised energy efficiency the heat pump is controlled by a configurable weather compensation system . The control box controls a supplementary electric heater or a standy-by boiler . The control box supplies power to the circulating pumps .
Heating system example : one heat emitter type with supplementary electric heating or stand-by boiler
Heating system |
P1 GT1 SV31 |
Back-up system |
GT ... |
|
|
P1 ...
SV ...
|
Hot water |
P2 |
Legend |
GT1 |
Water temperature loop 1 |
GT3 |
Outside air temperature |
P1 |
Pump for water loop 1 ( radiators ) |
P2 |
External water pump for the heat pump |
SV31 Three-way mixing valve for the back-up heater |
|
Accessory 00PPG000488100- Heating System Manager type B
HEATING
■■
Heating System Manager ( as accessory 00PPG000488000- ) two heat emitter types or independent zones and domestic hot water production :
--
Allows control of a non-reversible heating system that includes a 61WG heat pump and two different heat emitter types and / or two independent comfort zones . For optimised energy efficiency the heat pump is controlled by a configurable weather compensation system . The control box controls a supplementary electric heater or a standy-by boiler . The control box supplies power to the circulating pumps . Hot-water production can be permanent or programmable with a second setpoint at the heat pump and control of a switching valve .
Heating system example : two heat emitter types or independent zones and domestic hot water production
GT3
Heating system |
P1 |
SV31 |
Back-up system |
61WG + HSM |
|
|
GT1 |
|
|
|
|
GT7:2 |
|
|
GT4 |
SV34 |
|
P7-2 |
|
|
Legend |
P4
Floor heating
GT5
P5
|
SV35 |
GT7 |
GT2
SV32
|
GT ..
P ..
|
P2 |
Thermistors |
GT1 |
Water temperature loop 1 |
GT2 |
Domestic hot water tank temperature |
GT3 |
Outside air temperature |
GT4 |
Water temperature loop 2 |
GT5 |
Domestic hot water temperature |
GT7 |
Additional domestic hot water tank temperature |
Pumps |
P1 |
Pump for water loop 1 ( radiators ) |
P2 |
External water pump for the heat pump |
P4 |
Pump for water loop 2 ( floor heating ) |
P5 |
Pump to pre-heat the domestic hot water valve loop |
P7 |
Pump for domestic hot water circulation |
P7-2 |
Pump for domestic hot water circulation in an |
aditional tank |
|
Domestic hot water in |
P7 |
SV .. |
Hot water |
Valves SV31 Three-way mixing valve for the back-up heater SV32 Heating / domestic hot water change-over valve SV34 Three-way control valve for water loop 2 SV35 Three-way mixing valve for domestic hot water |
Notes : - This application example includes two zones and a supplementary boiler and domestic hot-water production . - The installation includes a switching valve ( SV32 ) that allows switching from the heat pump capacity of the heating system to domestic hot-water production . - The primary heating circuit is the domestic hot-water production circuit . It includes a tank with an equivalent pressure drop to simplify system balancing .
520