AHI Carrier Catalog | Page 434

Electrical data 30RQ 017 021 026 033 040 Power circuit Nominal power supply V-ph-Hz Control circuit supply * ** *** 400-3-50 ± 10% 24 V via internal transformer Maximum start-up current (Un)* A 75 95 118 118 176 Maximum operating power input** kW 7.8 9.1 11 13.8 17.5 Nominal unit operating current draw*** A 8 12 16 17 25 Maximum instantaneous start-up current (locked rotor current of the compressor). Power input, compressors and fans, at the unit operating limits (saturated suction temperature 10°C, saturated condensing temperature 65°C) and nominal voltage of 400 V (data given on the unit nameplate). Standardised Eurovent conditions: water heat exchanger entering/leaving water temperature 12°C/7°C, outside air temperature 35°C. Type key 30R Q - 021 C H E - B - - Revision status Product Range New option (not used) HEATING Q - Heat pump AquaSnap - - Standard A - Remote User Interface HMI Standard version - B C D Nominal capacity C - Power supply with neutral cable (not available for size 40) D - Power supply without neutral cable - Without gateway - CCN Jbus gateway - CCN Bacnet gateway - CCN LONtalk gateway Standard 0 H F R Z - Without hydronic module - With hydronic module with expansion tank - With hydronic module with expansion tank and water filling system - With hydronic module, without expansion tank - With hydronic module, w/o exp. tank, with water filling system 434 - - Without coil protection E - Epoxy coil-protection (Gold-fin) C A R R I E R 2 0 1 6 / 2 0 1 7