AHI Carrier Catalog | Page 430

AIR-TO-WATER HEAT PUMPS 30RQV 017-021 Available static system pressure Available static pressure, kPa Available external static pressure for 21kW unit with variable speed hydronic module HEATING Water flow rate, l/s Legend 1. Pump Speed = 100% 2. Pump Speed = 75% 3. Pump Speed = 50% 4. Pump Speed = 38% 5. Pump Speed = 25% BPHE water flow rate 30RQV units without hydronic module Minimum water flow rate, l/s Maximum water flow rate, l/s 17 0,45 1,3 21 0,57 1,5 30RQV units with fixed speed hydronic module Minimum water flow rate, l/s Maximum water flow rate, l/s 17 0,45 1,4 21 0,57 1,6 30RQV units with variable speed hydronic module Minimum water flow rate, l/s Maximum water flow rate, l/s 17 0,45 1,2 21 0,57 1,2 430 C A R R I E R 2 0 1 6 / 2 0 1 7