AHI Carrier Catalog | Page 42

Electrical data 30RB 008 012 015 Power circuit Nominal power supply V-ph-Hz 400-3-50 + neutral Voltage range V 376-424 Control circuit supply 24 V via internal transformer Maximum start-up current (Un)* A COOLING Unit power factor at nominal capacity** 30 66 73 0.88 0.84 0.85 Maximum operating power input** kW 3.1 4.4 5.5 Nominal unit operating current draw*** A 4.5 6.3 9.1 Power fuse current (gL fuse) A 10 16 20 Power supply cable section mm2 H07RN-F x 2.5 mm2 H07RN-F - 5 x 2.5 mm2 H07RN-F - 5 x 2.5 mm2 Maximum pump current (external pump or water circulator) A 2 2 2 1 2 2 H03VV-F - 7 x 0.5 mm2 H03VV-F - 7 x 0.5 mm H03VV-F - 7 x 0.5 mm Number of fan motor capacitors (5 μF/450 V) Power supply cable section, remote controller mm 2 * Maximum instantaneous start-up current (locked rotor current of the compressor). ** Power input, compressors and fans, at the unit operating limits (saturated suction temperature 10°C, saturated condensing temperature 65°C) and nominal voltage of 400 V (data given on the unit nameplate). *** Standardised Eurovent conditions: water heat exchanger entering/leaving water temperature 12°C/7°C, outside air temperature 35°C. Type key 30RB 008 - 9 B Revision status Liquid chilling packages 400 V 3-phases + N Unit options - With hydronic kit X Without hydronic kit Nominal size 008 - nominal size 8 kW 012 - nominal size 12 kW 015 - nominal size 15 kW Accessory Option Description Remote User Interface HMI Remotely installed user interface (via communication bus) Remote unit control up to 300 m 42 Advantages C A R R I E Use 30RB R 2 0 1 6 All sizes / 2 0 1 7