Electrical data
30RB
008
012
015
Power circuit
Nominal power supply
V-ph-Hz
400-3-50 + neutral
Voltage range
V
376-424
Control circuit supply
24 V via internal transformer
Maximum start-up current (Un)*
A
COOLING
Unit power factor at nominal capacity**
30
66
73
0.88
0.84
0.85
Maximum operating power input**
kW
3.1
4.4
5.5
Nominal unit operating current draw***
A
4.5
6.3
9.1
Power fuse current (gL fuse)
A
10
16
20
Power supply cable section
mm2
H07RN-F x 2.5 mm2
H07RN-F - 5
x 2.5 mm2
H07RN-F - 5
x 2.5 mm2
Maximum pump current (external pump or water circulator)
A
2
2
2
1
2
2
H03VV-F - 7
x 0.5 mm2
H03VV-F - 7
x 0.5 mm
H03VV-F - 7
x 0.5 mm
Number of fan motor capacitors (5 μF/450 V)
Power supply cable section, remote controller
mm
2
*
Maximum instantaneous start-up current (locked rotor current of the compressor).
** Power input, compressors and fans, at the unit operating limits (saturated suction temperature 10°C, saturated condensing temperature 65°C) and nominal voltage of 400 V (data given
on the unit nameplate).
*** Standardised Eurovent conditions: water heat exchanger entering/leaving water temperature 12°C/7°C, outside air temperature 35°C.
Type key
30RB
008 -
9
B
Revision status
Liquid chilling packages
400 V 3-phases + N
Unit options
-
With hydronic kit
X
Without hydronic kit
Nominal size
008 - nominal size 8 kW
012 - nominal size 12 kW
015 - nominal size 15 kW
Accessory
Option
Description
Remote User Interface HMI
Remotely installed user interface (via communication bus) Remote unit control up to 300 m