Dimensions/clearances
61AF 022-035 units with and without hydronic module
1110
300
1330
1327
1000
1000
Legend
All dimensions are in mm
Required clearances for air flow
Recommended space for maintenance
Water inlet
Water outlet
Air outlet, do not obstruct
1000
1000
Control box
Power cable connection
61AF 045-055 units with and without hydronic module
2100
1330
1114
300
1000
1000
1000
HEATING
1000
Notes:
A Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an installation. For the location of fixing points, weight distribution and
coordinates of the centre of gravity refer to the certified dimensional drawings.
B In multiple-unit installations (maximum four units), the side clearance between the units should be increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.