AHI Carrier Catalog | Page 41

AIR-COOLED LIQUID CHILLERS WITH INTEGRATED HYDRONIC MODULE  30RB 008-015 Physical data 30RB 008 012 015 Version without pump C1 Nominal capacity kW 7.95 10.83 13.99 Full load performances* C1 EER kW/kW 3.10 2.93 2.90 C1 Eurovent class cooling A B B C2 Nominal capacity kW 10.12 14.97 17.73 C2 EER kW/kW 3.69 3.65 3.44 C2 Eurovent class cooling B B D C3 Nominal capacity kW 5.1 7.0 8.4 C3 EER kW/kW 2.24 1.95 1.90 ESEER kW/kW 3.30 3.24 3.08 Seasonal efficiency* Version without pump C1 Nominal capacity kW 8.0 10.9 14.1 Full load performances** C1 EER kW/kW 3.17 3.01 3.00 C2 Nominal capacity kW 10.2 15.1 17.9 C2 EER kW/kW 3.83 3.80 3.59 C3 Nominal capacity kW 5.1 7.0 8.5 C3 EER kW/kW 2.27 1.98 1.93 COOLING Cooling Sound levels Sound power level(1) (C1) dB(A) 68 70 71 Sound pressure level at 4 m(2) (C1) dB(A) 48 50 51 Length mm 908 908 908 Depth mm 350 350 350 Height mm 821 1363 1363 Dimensions Operating weight(3) Unit without circulator (X version) kg 73.3 108 110 Unit with circulator (- version) kg 75.5 114 116 One hermetic rotary compressor One hermetic scroll compressor One hermetic scroll compressor Compressors Refrigerant kg 2.15 2.63 3.18 CO2 eq. 4.5 5.5 6.6 Air heat exchangers Copper tubes and aluminium fins Fans 3 blades fan Quantity 1 2 2 AIR TREATMENT R410A Circuit charge(3) Water heat exchanger (X version) Water pressure drop (C1) kPa 15 21 33 Water pressure drop (C2) kPa 28 36 49 Min. system water content l 28 42 52 Max. water-side operating pressure kPa 300 300 300 Hydronic module (- version) Pump Variable speed circulator Expansion tank volume l 2 2 2 Availabale static pressure (C1) kPa 52 74 60 Availabale static pressure (C2) kPa 37 54 33 Min. system water content l 28 42 52 Max. water-side operating pressure kPa 300 300 300 Diameter inch 1M 1M 1M Outside tube diameter mm 25.4 M 25.4 M 25.4 M HEATING HEATING Standard unit Chassis paint colour * ** C1 C2 C3 (1) (2) (3) C Beige In accordance with standard EN14511-3:2013 Not in accordance with standard EN14511-3:2013 Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W Cooling mode conditions: evaporator water entering/leaving temperature 23°C/18°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W Cooling mode conditions: evaporator water entering/leaving temperature 0°C/-5°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W, with 20% ethylene glycol In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with ISO 9614-1. In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from the sound power level Lw(A). Eurovent certified data Weights are guideline only. Refer to the unit nameplate. A R R I E R 2 0 1 6 / 2 0 1 7 41 CONTROLS Water connections with or without hydronic module