AIR-COOLED LIQUID CHILLERS WITH
INTEGRATED HYDRONIC MODULE 30RB 008-015
Physical data
30RB
008
012
015
Version without pump
C1
Nominal capacity
kW
7.95
10.83
13.99
Full load performances*
C1
EER
kW/kW
3.10
2.93
2.90
C1
Eurovent class cooling
A
B
B
C2
Nominal capacity
kW
10.12
14.97
17.73
C2
EER
kW/kW
3.69
3.65
3.44
C2
Eurovent class cooling
B
B
D
C3
Nominal capacity
kW
5.1
7.0
8.4
C3
EER
kW/kW
2.24
1.95
1.90
ESEER
kW/kW
3.30
3.24
3.08
Seasonal efficiency*
Version without pump
C1
Nominal capacity
kW
8.0
10.9
14.1
Full load performances**
C1
EER
kW/kW
3.17
3.01
3.00
C2
Nominal capacity
kW
10.2
15.1
17.9
C2
EER
kW/kW
3.83
3.80
3.59
C3
Nominal capacity
kW
5.1
7.0
8.5
C3
EER
kW/kW
2.27
1.98
1.93
COOLING
Cooling
Sound levels
Sound power level(1) (C1)
dB(A)
68
70
71
Sound pressure level at 4 m(2) (C1)
dB(A)
48
50
51
Length
mm
908
908
908
Depth
mm
350
350
350
Height
mm
821
1363
1363
Dimensions
Operating weight(3)
Unit without circulator (X version)
kg
73.3
108
110
Unit with circulator (- version)
kg
75.5
114
116
One hermetic rotary
compressor
One hermetic scroll
compressor
One hermetic scroll
compressor
Compressors
Refrigerant
kg
2.15
2.63
3.18
CO2 eq.
4.5
5.5
6.6
Air heat exchangers
Copper tubes and aluminium fins
Fans
3 blades fan
Quantity
1
2
2
AIR TREATMENT
R410A
Circuit charge(3)
Water heat exchanger (X version)
Water pressure drop (C1)
kPa
15
21
33
Water pressure drop (C2)
kPa
28
36
49
Min. system water content
l
28
42
52
Max. water-side operating pressure
kPa
300
300
300
Hydronic module (- version)
Pump
Variable speed circulator
Expansion tank volume
l
2
2
2
Availabale static pressure (C1)
kPa
52
74
60
Availabale static pressure (C2)
kPa
37
54
33
Min. system water content
l
28
42
52
Max. water-side operating pressure
kPa
300
300
300
Diameter
inch
1M
1M
1M
Outside tube diameter
mm
25.4 M
25.4 M
25.4 M
HEATING HEATING
Standard unit
Chassis paint colour
*
**
C1
C2
C3
(1)
(2)
(3)
C
Beige
In accordance with standard EN14511-3:2013
Not in accordance with standard EN14511-3:2013
Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W
Cooling mode conditions: evaporator water entering/leaving temperature 23°C/18°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W
Cooling mode conditions: evaporator water entering/leaving temperature 0°C/-5°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W, with 20% ethylene glycol
In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
Measured in accordance with ISO 9614-1.
In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
For information, calculated from the sound power level Lw(A).
Eurovent certified data
Weights are guideline only. Refer to the unit nameplate.
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
41
CONTROLS
Water connections with or without hydronic module