Power circuit Nominal power supply |
V-ph-Hz |
400-3-50 ± 10 % |
||||||
Control circuit supply |
24 V , via internal transformer |
|||||||
Maximum start-up current ( Un )* |
||||||||
Standard unit |
A |
104 |
102 |
130 |
170 |
190 |
157 |
229 |
Unit with electronic starter option |
A |
56 |
55 |
70 |
91 |
101 |
101 |
142 |
Unit power factor at maximum capacity ** |
0.82 |
0.82 |
0.82 |
0.82 |
0.82 |
0.82 |
0.82 |
|
Maximum unit power input ** |
kW |
8.7 |
11.6 |
12.9 |
14.6 |
16.8 |
25.8 |
33.7 |
Nominal unit current draw *** |
A |
13.6 |
16.4 |
20.1 |
23.2 |
27.7 |
40.2 |
55.4 |
Maximum unit current draw ( Un )**** |
A |
16.8 |
21.1 |
27.0 |
32.8 |
38.8 |
54.0 |
77.6 |
Corrosion protection , traditional |
3A |
Fins made of pre-treated aluminium ( polyurethane
Improved corrosion resistance , recommended for
61AF 022-105
|
||
coils |
and epoxy ) |
moderate marine and urban environments |
||
Unit with discharge air ducts |
11 |
Fans with available pressure - max . 100 Pa |
Enhances unit adjustment during installation ( e . g .
61AF 035-105 under a roof )
|
|
Low noise level |
15 |
Aesthetic and sound absorbing compressor
Noise level reduction by 1 to 2 dB ( A )
|
61AF 022-105 |
|
enclosure |
||||
Very low noise level |
15LS |
Aesthetic and sound absorbing compressor
Noise level reduction by 6 to 7 dB ( A )
|
61AF 035-105 |
|
enclosure associated with low-speed fans |
||||
Soft Starter |
25 |
Electronic starter on each compressor |
Reduced start-up current |
61AF 022-105 |
Frost protection down to -20 ° C |
42 |
Electric heater on the hydronic module |
Hydronic module frost protection at low outside
61AF 022-105
|
|
temperatures |
with option 116X |
|||
Master / slave operation |
58 |
Unit equipped with supplementary water outlet
Optimised operation of two chillers connected in
61AF 022-105
|
||
temperature sensor kit to be |
parallel with operating time equalisation |
|||
LP variable-speed single-pump |
116X |
field-installed allowing master / slave operation of
Easy and fast installation
|
61AF 022-105 |
|
two units connected in parallel |
||||
J-Bus gateway |
148B |
See hydronic module chapter |
Connects the unit by communication bus to a
61AF 022-105 building management system
|
|
BacNet gateway |
148C |
Two-directional communication board complying
Easy connection by communication bus to a
61AF 022-105
|
||
with JBus protocol |
building management system |
|||
Lon gateway |
148D |
Two-directional communication board complying
Connects the unit by communication bus to a
61AF 022-105
|
||
with BacNet protocol |
building management system |
|||
Compliance with Russian |
199 |
Two-directional communication board complying
Conformance with Russian regulations
|
61AF 022-105 |
|
regulations |
with Lon Talk protocol |
|||
Condenser screw connection |
265 |
EAC certification |
Allows unit connection to a screw connector |
61AF 035-105 |
sleeves |
||||
Welded condenser water connection kit |
267 |
Condenser inlet / outlet screw connection sleeves |
Easy installation |
61AF 035-105 |
Remote user interface |
275 |
User interface for remote installation |
Remote control of the unit and its operating
61AF 022-105 parameters
|
Heating system control facilitated |
61AF 022-105 |
|||||||||||||||||
Heating system control facilitated |
61AF 022-105 |
|||||||||||||||||
Heating system control facilitated |
61AF 022-105 |
|||||||||||||||||