COMFORT MODULE RANGE FOR
MONOBLOC HEAT PUMPS 80HMA
Physical data
Indoor unit (comfort module)
80HMA-M00
80HMA-M03
80HMA-M06
80HMA-T06
80HMA-T09
1
1
1
1
1
0
3
6
6
9
Number of auxiliary heating steps
1 (external boiler)
1
3
3
3
Connection of back-up boiler
Yes
No
No
No
No
Number of comfort zones
kW
Electric booster element
Dimensions, H x L x D
mm
800 x 450 x 320
800 x 450 x 320
800 x 450 x 320
800 x 450 x 320
800 x 450 x 320
Operating weight
kg
34
35
35
35
35
Power supply
V-ph-Hz
230-1-50
230-1-50
230-1-50
400-3-50
400-3-50
C6
C20
C32
C16
C20
Recommended circuit breaker size
Combination table, indoor and outdoor units
Outdoor unit (heat pump)
Indoor unit (comfort module)
Nominal capacity 4 kW
80HMA-M00
Reversible, 1 zone, maximum heating capacity 20 kW for boiler
back-up application
30AWH06HC
Nominal capacity 6 kW
80HMA-M03
Reversible, 1 zone, maximum heating capacity 20 kW with
3 kW 1-phase electrical heater booster
30AWH08HC
Nominal capacity 8 kW
80HMA-M06
Reversible, 1 zone, maximum heating capacity 20 kW with
6 kW 1-phase electrical heater booster
30AWH12HC
Nominal capacity 12 kW
80HMA-T06
Reversible, 1 zone, maximum heating capacity 20 kW with
6 kW 3-phase electrical heater booster
30AWH12HC9
Nominal capacity 12 kW
80HMA-T06
Reversible, 1 zone, maximum heating capacity 20 kW with
6 kW 3-phase electrical heater booster
30AWH15HC
Nominal capacity 15 kW
80HMA-T09
Reversible, 1 zone, maximum heating capacity 20 kW with
9 kW 3-phase electrical heater booster
30AWH15HC9
Nominal capacity 15 kW
80HMA-T09
Reversible, 1 zone, maximum heating capacity 20 kW with
9 kW 3-phase electrical heater booster
HEATING
30AWH04HC
Note: All 30AWH sizes are compatible with the 80HMA comfort module range. Comfort module controls can also manage up to eight 30AWH units. A parallel hydronic coupling of the unit
to a tank is necessary (field supply). 30RQ 017 to 021 and 61AF 014 to 019 units are also compatible, but the water volume of this installation must be checked by a professional and
comply with the heat pump size minimum requirements. Depending on the terminal unit type installed with the Carrier system a buffer tank may have to be added.
M00
M03
M06
T06
T09
Power supply
V-ph-Hz
230-1-50
230-1-50
230-1-50
400-3-50
400-3-50
Voltage range
V
207-253
207-253
207-253
360-400
360-400
Max. power consumption, board and auxiliary devices
kW
Board and auxiliary circuit breaker protection (not included)
kW
Electric heater power consumption
Electric heater circuit breaker protection (not included)
1.15
1.15
1.15
1.15
1.15
C6
C6
C6
C6
C6
0
3
6
6
9
C6
C20
C32
C16
C20
Max. operating current
A
5
18
31
14
18
Main power cable size
mm2
3G x 2.5
3G x 4
3G x 6
5G x 2.5
5G x 4
Communication cable (FROH2R)
mm
2
2 x 0.75
2 x 0.75
2 x 0.75
2 x 0.75
2 x 0.75
User interface (additional or remote) cable (FROH2R)
mm2
4 x 0.75
4 x 0.75
4 x 0.75
4 x 0.75
4 x 0.75
Booster heater power supply cable (H05VV-F)
mm2
3G x 2.5
3G x 2.5
3G x 2.5
3G x 2.5
3G x 2.5
Booster heater activation cable (FROH2R)
mm
2x1
2x1
2x1
2x1
2x1
Domstic hot water sensor cable (FROH2R)
mm2
2 x 0.5
2 x 0.5
2 x 0.5
2 x 0.5
2 x 0.5
Remote o utdoor sensor cable (FROH2R)
mm
2 x 0.5
2 x 0.5
2 x 0.5
2 x 0.5
2 x 0.5
Note: The heat pump data depends on the heat pump used.
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
2
2
CONTROLS
Comfort module 80HMA
AIR TREATMENT
Electrical data
387