AIR-TO-WATER HEAT PUMP HEATING SYSTEM 38AW/80AW
Physical data
38AW/80AW
Outdoor unit (heat pump)
Indoor unit (comfort module)
38AW
38AW
38AW
38AW
38AW
38AW
050H7
065H7
090H7
115H7
120H9
150H9
80AWH
80AWH
80AWH
80AWH
80AWH
80AWH
065
065
115
115
150
150
3.57
4.73
5.95
6.80
10.30
12.60
Cooling (80AWX only)
Full load
performances*
C1
Nominal capacity
kW
kW/kW
C1
EER
C1
Eurovent class cooling
C2
Nominal capacity
kW
C2
EER
kW/kW
C2
Eurovent class cooling
Seasonal
efficiency*
ESEER
kW/kW
2.60
2.60
3.07
2.88
3.41
3.17
D
D
B
C
A
A
5.10
6.55
7.88
9.00
13.50
15.79
3.40
3.40
4.05
3.80
4.74
4.24
D
D
A
A
A
A
3.71
3.71
4.45
4.37
4.56
4.79
Seasonal
efficiency**
(80AWX only)
Seasonal
efficiency**
(80AWH only)
H1
Nominal capacity
kW
5.01
6.55
9.27
11.50
12.00
15.01
H1
COP
kW/kW
4.15
4.15
4.48
4.10
4.65
4.30
H1
Eurovent class cooling
A
A
A
A
A
A
H2
Nominal capacity
kW
4.37
5.70
8.70
11.30
11.20
14.02
H2
COP
kW/kW
3.41
3.34
3.45
3.32
3.70
3.40
H2
Eurov ent class cooling
A
A
A
A
A
A
H3
Nominal capacity
kW
4.25
5.52
7.88
10.95
11.48
11.91
H3
COP
kW/kW
2.65
2.86
2.90
2.79
3.12
3.10
H3
SCOP
kW/kW
3.00
2.98
2.99
2.94
3.45
3.29
H3
Ƞs heat
%
117
116
117
115
135
128
H3
Prated
kW
1.90
2.16
7.60
8.75
8.37
9.38
H3
Annual energy
consumption
kWh
1303
1494
5245
6143
5004
5897
A+
A+
A+
A+
A++
A++
kW/kW
2.81
2.81
2.94
2.90
3.39
3.24
H3
Energy efficiency class
H3
SCOP
H3
Ƞs heat
%
110
110
115
113
133
127
H3
Prated
kW
1.90
2.16
7.60
8.75
8.37
9.38
H3
Annual energy
consumption
kWh
1303
1494
5245
6143
5004
5897
H3
Energy efficiency class
A+
A+
A+
A+
A++
A++
AIR TREATMENT
Full load
performances*
HEATING
Heating (80AWX and 80AWH)
CONTROLS
*
In accordance with standard EN14511-3:2013
** In accordance with standard EN14825:2013, average climate
C1 Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W
C2 Cooling mode conditions: evaporator water entering/leaving temperature 23°C/18°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W
H1 Heating mode conditions: Water heat exchanger water entering/leaving temperature 30°C/35°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
H2 Heating mode conditions: Water heat exchanger water entering/leaving temperature 40°C/45°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
H3 Heating mode conditions: Water heat exchanger water entering/leaving temperature 47°C/55°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
(1) In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
Measured in accordance with ISO 9614-1.
(2) In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
For information, calculated from the sound power level Lw(A).
(3) Weights are guideline only. Refer to the unit nameplate.
Eurovent certified data
Eurovent certified data
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1