AHI Carrier Catalog | Page 347
DOUBLE-EFFECT STEAM-FIRED ABSORPTION CHILLERS
16NK 11-81
Physical data
16NK
11
12
13
21
22
31
32
41
42
kW
345
447
549
689
861
1034
1238
1378
1551
Flow rate
l/s
14.8
19.2
23.6
29.7
37.2
44.4
53.3
59.4
66.7
Pressure drop
kPa
44
64
64
57
42
41
49
46
41
Connection (ANSI)
in
4
4
4
5
6
6
6
8
8
Retention volume
m3
0.13
0.15
0.17
0.24
0.28
0.34
0.36
0.46
0.48
Flow rate
l/s
24.7
31.9
39.4
49.4
61.9
74.2
88.9
98.9
111.4
Pressure drop
kPa
68
40
49
109
74
53
65
67
73
Connection (ANSI)
in
5
5
5
6
8
8
8
10
10
Retention volume
m
0.34
0.38
0.42
0.58
0.63
0.89
0.95
1.11
1.9
1180
1410
1570
1770
Cooling capacity
3
Steam system
Saturated steam 784 kPa
Consumption
kg/h
Dimensions
mm
400
510
630
790
980
Length A
2810
3850
3850
3880
4920
5040
5040
5100
5100
Height B
2200
2200
2200
2250
2250
2390
2390
2600
2600
Width C
2050
1910
1910
2240
2070
2170
2170
2400
2400
Operating weight
kg
4600
5800
6100
7500
8800
11200
11800
13900
14500
Power supply
V-ph-Hz
400-3-50
Total current drawn
A
10.8
10.8
10.8
13.3
13.3
13.6
13.6
20.7
20.7
51
52
53
61
62
63
71
72
81
kW
1723
1927
2170
2412
2757
3101
3446
3963
4652
Flow rate
l/s
74.2
83.1
93.9
103.9
118.6
133.6
148.3
170.6
200.3
Pressure drop
kPa
98
46
61
123
83
78
54
81
84
Connection (ANSI)
in
8
8
8
10
10
10
12
12
14
Retention volume
m3
0.65
0.71
0.77
0.99
1.06
1.13
1.41
1.61
1.94
Flow rate
l/s
123.6
138.3
155.6
173.1
197.8
222.5
247.2
284.4
333.9
Pressure drop
kPa
53
71
94
61
83
111
77
113
122
Connection (ANSI)
in
12
12
12
14
14
14
16
16
16
Retention volume
m3
1.87
2.01
2.14
2.79
2.97
3.15
3.67
4.11
4.76
3530
3920
4510
5300
16NK
Cooling capacity
Chilled water system*
HEATING HEATING
Cooling water system*
COOLING
Chilled water system*
Steam system
Saturated steam 784 kPa
Consumption
kg/h
Dimensions
mm
1960
2200
2470
2750
3140
Length A
5330
5870
6370
6100
6190
6710
6440
7460
7460
Height B
2900
2900
2900
3330
3330
3330
3450
3450
3650
Width C
2770
2800
2800
2970
3000
3000
3300
3300
3500
Operating weight
kg
18800
20800
22300
26500
30000
32100
38000
42300
47300
Power supply
V-ph-Hz
400-3-50
Total current drawn
A
22.7
24.5
24.5
25.5
25
25
33.5
33.5
33.5
AIR TREATMENT
Cooling water system*
CONTROLS
Cooling per ARI 560 2000:
*
12.2 —> 6.7°C (fouling factor = 0.0176 m2 K/kW)
** 29.4 —> 35.4°C (fouling factor = 0.044 m2 K/kW)
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
347